Plan Review Notes
Plan Review Notes For Permit 13090021
Permit Number 13090021
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-09-05 19:39:255829 CORPORATE WAY
 PERMIT #13090021
 REVIEW COMMENTS - FIRE DEPARTMENT
 REFERENCE: NFPA 101 - CHAPTER 13 EXISTING ASSEMBLY &
 CHAPTER 15 EXISTING EDUCATIONAL OCCUPANCIES
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2009 EDITION WITH FLORIDA AMENDMENTS.)
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 THE BUILDING IS DESIGNED AND FUNCTIONING AS A MULTIUSE
 NON-SEPARATED OCCUPANCY (ASSEMBLY, EDUCATIONAL AND
 BUSINESS OCCUPANCIES) . FOR NON-SEPARATED MIXED USE
 OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE SAFETY
 REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO THE
 BUILDING. PER SECTION 6.1.14.1.2, WHERE EXIT ACCESS
 FROM AN OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, THE
 MULTIPLE OCCUPANCY SHALL BE TREATED AS A MIXED
 OCCUPANCY. CURRENTLY THE TWO LARGE ASSEMBLY ROOMS
 (MULTIPURPOSE AND CAFETERIA) HAVE EGRESS THAT TRAVERSES
 ANOTHER OCCUPANCY. PER SECTION 13.3.4, PROVIDE
 SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300
 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 EXISTING ENTRANCE LOBBY DOORS NOT EQUIPPED WITH PANIC
 HARDWARE. INDICATE ALL DOORS (NEW AND EXISTING) TO BE
 EQUIPPED WITH PANIC/FIRE EXIT HARDWARE. FOR ASSEMBLY
 AND EDUCATIONAL OCCUPANCIES WITH AN OCCUPANT LOAD OF
 100 OR MORE PERSONS (50 PERSONS PER THE FLORIDA
 BUILDING CODE), PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE.
  
 EXISTING EXTERIOR EXIT DOOR FROM CAFETERIA WILL NEED A
 RAMP OR SIDEWALK AS THE CURRENT EXIT DISCHARGE HAS A
 STEP DOWN TO PAVERS SPACED ABOUT 2 FEET APART LEADING
 TO THE PARKING LOT.
  
 NO EMERGENCY LIGHTING PROVIDED FOR SECOND FLOOR
 CORRIDOR ADJACENT TO WOMENS' RESTROOM.
  
 PROVIDE A FURNITURE AND SEATING PLAN.
  
 PLANS INDICATE A KITCHEN. INDICATE WHAT COOKING
 EQUIPMENT IS INTENDED AND THE COOKING OPERATIONS THAT
 WILL BE PERFORMED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED
 WALL ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM
 OR DEVICE.
  
 NO MECHANICAL PLANS SUBMITTED SHOWING FIRE DAMPERS.
  
 POST PERMANENT SIGNAGE IN THE STAIRS INDICATING "NO
 STORAGE PERMITTED BY ORDER OF THE FIRE MARSHAL."
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  