2013-09-10 16:39:18BUILDING PLAN REVIEW
 PERMIT: 13090021
 ADD: 5829 CORPORATE WAY
 CONT: JJ MORLEY ENTERPRISES
 TEL: (561)843-5325
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SEPTEMBER 10/ 2013
 ACTION: DENIED
  
 1) SHEET A1:
 1A) HEADING: SCOPE OF WORK (1) TO INSTALL A NEW 1 HOUR
 FIRE RATED CORRIDOR WALLS AND 1 HOUR FIRE RATED CEILING
 AS SHOWN ON PLANS. SHEET A1 DETAIL 1/ SHEET A2
 INDICATES THE USE OF A 1 HOUR FIRE RATED CEILING
 INSTEAD OF THE CORRIDOR WALLS GOING ALL THE WAY TO THE
 DECK ABOVE. THE DETAIL INDICATES THE CEILING TO FOLLOW
 THE UL LISTING 469. THE ONLY SHAFT WALL LISTED UNDER
 469 IS U-469 SHAFT WALL CONSTRUCTION FOR VERTICAL USE.
 THE 2010 FBC-B FIRE PARTITIONS 709.4 EXCEPTION # 3 DOES
 ALLOW FOR THE USE OF FIRE RATED WALL DESIGN TO BE USED
 FOR FIRE RATED CEILINGS AND THE UL- U 469 DOES NOT
 INDICATE HOW THIS CONSTRUCTION IS TO APPEAR, THE 2007
 FL CODE COMMENTARY FIGURE 708.4(2)(C) DOES SHOW HOW THE
 WALL MEMBERS, CEILING MEMBERS & DRYWALL LAPS ARE
 CONSTRUCTED TO MAINTAIN A 1 HOUR FIRE RATING.
  
 1B) DOOR NOTE # 5 INDICATES ALL DOORS SHALL HAVE LEVER
 TYPE HARDWARE. PLEASE PROVIDE THE HARDWARE TYPE ON THE
 EXISTING DOORS STIARWAYS, AND LOBBY AREA, THEY WILL
 ALSO NEED TO COMPLY WITH 2010 FBC-B 1008.1.10 PANIC
 HARDWARE REQUIRED WHEN SERVING A A OR E OCCUPANCY WITH
 AN OCCUPANT LOAD OF 50 OR MORE.
  
 1C) MULTI-PURPOSE ROOM SHOWS A NEW EXIT DOOR, PLEASE
 PROVIDE THE MEANS OF EXITING TO THE PUBLIC WAY,
 (LANDING & SIDEWALK) FOR THIS NEW DOOR AND THE EXTERIOR
 DOOR IN THE CAFETERIA. FBC- B 1027.6 ACCESS TO THE
 PUBLIC WAY.
  
 1D) THE NEW EXIT DOOR IN THE MULTI-MEDIA ROOM WILL
 REQUIRE PRODUCT APPROVAL PER : 2010 FBC FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS & (31)(B) WINDOWS.
  
 1E) 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 1F) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1F) (1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED
 IN ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1F) (2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 1F) (3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1F) (4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1F) (5) COMPONENTS & CLADDING PRESSURES POSITVE &
 NEGATIVE TABLE 1609.2(2) .
  
 1G) THE PLANS INDICATE EXISTING KITCHEN, THE LAST KNOWN
 USE INDICATED THIS TO BE A BREAK ROOM. PLEASE PROVIDE
 WHAT TYPE OF COOKING EQUIPMENT IS LOCATED IN THIS ROOM?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) INFORMATION REQUIRED BY 2010 FBC-B NOT LOCATED ON
 PLANS:
 2A) 443.2.2 PLAYGROUND & EQUIPMENT.
  
 2B) 443.2.3 OUTDOOR WAST CONTAINERS.
  
 2C) 443.3.2 GLARE FROM NATURAL LIGHT. 443.3.7.5 GLARE
 ELIMINATION.
  
 2D) 443.3.3 AGE NOT PROVIDED FOR EDUCATIONAL OCCUPANCY
  
 2E) 443.3.4. AGE NOT PROVIDED FOR EDUCATIONAL
 OCCUPANCY.
  
 2F) 443.3.5.2 TEACHER TOLIETS
  
 2G) 443.3.5.5 WALLS IN KITCHENS, SCULLERY,AND CAN WASH
 AREAS ARE TO BE IMPERVIOUS TO A HEIGHT OF AT LEAST
 6'-0".
  
 2H) 443.3.5.6 FLOOR DRAINS AND HOSE BIBBS. GROUP TOLIET
 ROOMS.
  
 2I) 443.3.6.5 CHEMICAL STORAGE.
  
 2J) 443.3.7 (1-5) LIGHTING
  
 3) SHEET A2:
 3A) ON THE 2ND FLOOR THE EXISITNG EMERGENCY WINDOWS
 PLEASE PROVIDE OPENING SIZE OF WINDOWS. FBC-B 1029.4.1.
  
 3B) SHEET A2 & LS 2 INDICATE THE USE OF A AREA OF
 RESCUE ASSISTANCE AND THE TWO WAY COMMUNICATION WITHIN
 THE STAIRWWELL. NOTE THE COOMUNICATION DEVICE IS
 LOCATED BEHIND THE OCCUPANT IN THE WHEELCHAIR. ALSO
 NOTE THEIR IS NO CCOMMUNICATION DEVICE INDICATED ON THE
 FIRSTFLOOR NOR IS THERE ANY IDENTIFICATION ON THE
 EXTERIOR FIRST FLOOR THEIR IS A AREA OF RESCUE
 ASSISTANCE.
  
 3C) PLEASE PROVIDE A CUT SECTION THROUGH THE STAIRWELL
 WHERE THE NEW AREA OF RESCUE PLATFORM IS LOCATED,
 PROVIDE THE CLEARANCE FROM THE STAIR TREAD TO THE
 LEADING EDGE OF THE PLATFORM. 2010 FBC-B 1009.2.
  
 3D) PLEASE PROVIDE THE STRUCTURAL DETAILS HOW THE
 PLATFORM AND GAURD RAILS WILL MEET FBC-B TABLE 1607.1
 LIVE LOADS, & 1607.7.1, 1607.7.1.1 & 1607.7.1.2.
  
 4) PLEASE PROVIDE WHERE AND ADDITIONAL $15,000.00 WILL
 BE USED IN UPDATING THE BUILDING TO MEET TODAYS
 STANDARDS IN ACCESSIBILITY, PLEASE REVIEW 202.4 AND
 202.4.1 DISPROPORTIONATE COST.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676