| 2013-10-11 13:56:10 | PLANS DENIED | | | 1) PROVIDE CALCULATION OF HEATING AND COOLING LOADS | | | PER SECTION 503.2.1 2010 ENERGY CODE | | | 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS. | | | 2) REFER TO SECTION 503.2.6 EXHAUST AIR ENERGY | | | RECOVERY FOR COOLING SYSTEM. 2010 FLORIDA ENERGY CODE. | | | 3 PROVIDE NOA FOR ALL OUTSIDE GRILLS. | | | SECTION107.3.4.1 FBC 2010 | | | 4) REFER TO SECTION 607.5.5 PROVIDE WHAT TYPE OF FIRE | | | PROTECTION IS BEING | | | USED FOR DRYER EXHAUST AND BATH EXHAUST IN THE SHAFT | | | 2010 FBC (M) | | | 5) REFER TO SECTION1107.2.1 PIPING IN CONCRETE FLOORS. | | | 6) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S | | | 7) PROVIDE A DETAIL ON HOW THE CURBS FOR THE RTU ARE | | | TIED DOWN TO THE ROOF | | | AND HOW THE RTU IS TIED TO THE CURB. PER SECTION 3.1.12 | | | WIND RESISTANCE | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | |
|