2013-09-20 13:23:48300 PALM BEACH LAKES BLVD
 PERMIT #13081230
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1. PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
 2. PLEASE SPECIFY IF BUILDING IS SEPARATED OR
 NON-SEPARATED USE.
 3. PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
 4. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
 5. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 6. TACTILE SIGNAGE IS NEEDED FOR EXIT DOORS.
 7. PER SECTION 7.2.2.5.4 - STAIRWAY IDENTIFICATION: NEW
 ENCLOSED STAIRS SERVING THREE OR MORE STORIES AND
 EXISTING ENCLOSED STAIRS SERVING FIVE OR MORE STORIES
 SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS ?NO ROOF ACCESS? AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER ?B?
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
 8. INCLUDE DOMESTIC DEMAND IN HYDRAULIC CALCULATIONS
 FOR AUTOMATIC SPRINKLER SYSTEM.
 9. THE FIFTH FLOOR APPEARS TO BE A GATHERING AREA WHICH
 MAY RESULT IN AN ASSEMBLY OCCUPANCY IN WHICH TWO EXITS
 ARE REQUIRED.
 10.PROVIDE DOOR TAGS ON THE FLOOR PLAN THAT COORESPOND
 WITH THE DOOR SCHEDULE.
 11.THE DOOR FOR ELECTRICAL ROOM 109 IS EXPOSED TO THE
 EXTERIOR STAIR AND SHOULD BE RATED.
 12. THE DOORS TO TRANSOM 111 AND ELECTRICAL ROOM 110
 ARE EXPOSED TO THE EXIT DISCHARGE AND SHOULD BE RATED.
 13. PROVIDE FIRE ALARM NOTIFICATION FOR ROOFTOP AND
 PATIO AREAS.
 14. PROVIDE LOW ELEVATION EXIT SIGNAGE AND LIGHTING FOR
 ROOFTOP AND PATIO AREAS.
 15. SHEET E.2.1 - KEYED NOTES ARE NOT VISIBLE
 16. SHEET E.2.1 - PLAN INDICATES FIRE ALARM SPEAKER. IS
 THIS FOR VOICE OR HORN EVACUATION?
 17. SHEETS E.0.1 /E.2.1 - CONFLICT OF SYMBOL
 REPRESENTATION. SHEETS INDICATE VISUAL SIGNALING UNIT
 WALL MOUNTED (NO AUDIBLE)
 18. SHEET E.2.2 - INDICATES KEYED NOTE "8" COMPLETELY
 DIFFERENT SYMBOL REPRESENTATION FOR FIRE ALARM
 NOTIFICATION - UNIT B
 19. ADD SMOKE ALARM IMMEDIATELY OUTSIDE BEDROOM
 ADJACENT TO THE SECOND FLOOR BEDROOM - UNIT A
 20. E.3.1 - PER LOCAL AMENDMENTS, DUCT DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION
 21. THE BUILDING IS TO BE PROTECTED BY NFPA 13 SYSTEM.
 A 13-R SYSTEM IS NOT APPLICABLE AS THE BUILDING EXCEEDS
 FOUR STORIES IN HEIGHT.
 22. STANDPIPE IS NOT PERMITTED TO BE ROUTED THROUGH
 ELECTRICAL ROOM 109
 23. FP.1.1 - NE STAIR - CONFIRM 6" STANDPIPE AND FIRE
 DEPARTMENT VALVE TO NO IMPEDE THE PATH OF EGRESS TO
 EXTERIOR DOOR.
 24. PROVIDE 2HR RATED VERTICAL SHAFT FOR STANDPIPE
 SERVING THE EXTERIOR STAIR.
 25. STANDPIPE AND HOSE VALVE FOR EXTERIOR STAIR SHOULD
 BE EXTENDED TO THE ROOF.
  
  
 LAUREN PHILMORE