Plan Review Notes
Plan Review Notes For Permit 13081230
Permit Number 13081230
Review Stop E
Sequence Number 1
Notes
Date Text
2013-11-14 16:05:46IT IS NOT THE INTENT OF THIS REVIEW TO PROVIDE A "PUNCH
 LIST" FOR THE DESIGN PROFESSIONAL, BUT A PRELIMINARY
 REVIEW INDICATED THE FOLLOWING:
 1. THE KEYED NOTES AS SHOWN ON THE PLANS ARE NOT
 IDENTIFIABLE.
 2. NEC 240.24(D) PROHIBITS THE ELECTRICAL PANEL FROM
 BEING INSIDE A CLOTHES CLOSET.
 3. NEC 210.52(A)(1) REQUIRES LIGHTING IN-THE FRONT ROOM
 AS YOU EXIT THE STAIRS
 4. NEC 210.70(A)(3) REQUIRES LIGHTING IN THE UTILITY
 ROOM WHERE THE WATER HEATER IS AT.
 5. NEC 210.52(E)(3) REQUIRES AN OUTLET IN THE BALCONY
 BECAUSE IT IS GREATER THAN 20 SQ. FT.
 THERE ARE TWO SEPARATE INDIVIDUAL APARTMENT UNIT LOAD
 CALCS AS EXPRESSED ON THE PLANS AND THEY DO NOT MATCH.
  