| 2013-11-14 16:05:46 | IT IS NOT THE INTENT OF THIS REVIEW TO PROVIDE A "PUNCH | | | LIST" FOR THE DESIGN PROFESSIONAL, BUT A PRELIMINARY | | | REVIEW INDICATED THE FOLLOWING: | | | 1. THE KEYED NOTES AS SHOWN ON THE PLANS ARE NOT | | | IDENTIFIABLE. | | | 2. NEC 240.24(D) PROHIBITS THE ELECTRICAL PANEL FROM | | | BEING INSIDE A CLOTHES CLOSET. | | | 3. NEC 210.52(A)(1) REQUIRES LIGHTING IN-THE FRONT ROOM | | | AS YOU EXIT THE STAIRS | | | 4. NEC 210.70(A)(3) REQUIRES LIGHTING IN THE UTILITY | | | ROOM WHERE THE WATER HEATER IS AT. | | | 5. NEC 210.52(E)(3) REQUIRES AN OUTLET IN THE BALCONY | | | BECAUSE IT IS GREATER THAN 20 SQ. FT. | | | THERE ARE TWO SEPARATE INDIVIDUAL APARTMENT UNIT LOAD | | | CALCS AS EXPRESSED ON THE PLANS AND THEY DO NOT MATCH. | | | |
|