| 2013-09-23 15:08:25 | BUILDING PLAN REVIEW |
| | PERMIT:13081230 |
| | ADD: 300 PALM BEACH LAKES |
| | CONT: DALL CONSRUCTION CO |
| | TEL: (305)458-8314 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 9/23/2013 |
| | ACTION: DENIED |
| | |
| | THE PLANS SUBMITTED ARE MORE OF A RENDERING THAN |
| | BUILDABLE SET OF PLANS PLEASE BE AWARE A THOROUGH |
| | REVIEW CAN NOT BE MADE AT THIS TIME, AS A RESULT OF THE |
| | ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS |
| | MAY APPEAR THAT WERE NOT PART OF THIS REVIEW.' |
| | 1) THIS BUILDING MEETS THE DEFINITION OF A THRESHOLD |
| | BUILDING. THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) |
| | " THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF |
| | THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR |
| | FURTHER INFORMATION AND FORMS BEFORE THE PERMIT MAY BE |
| | ISSUED. |
| | |
| | 1C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 109.3.6.4.4 |
| | ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE-SAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 1D) A PLAN REVIEW STOP (THRESHOLD) WILL BE PUT ON THIS |
| | PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY |
| | THE CHIEF BUILDING INSPECTOR KEN CONRAD: PLEASE CALL |
| | THE CITY OF WEST PALM BEACH'S AUTOMATED TELEPHONE |
| | INSPECTIONS LINE (561) 805-6700) FOR IN-PROGRESS |
| | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS. |
| | |
| | 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 1F) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 1G) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 1H) THREE SETS OF PLANS AND PRODUCT TESTING REPORTS |
| | WILL BE REQUIRED, SINCE THIS IS A THRESHOLD BUILDING. |
| | |
| | 2) SHEET A0.0 PROJECT DATA: |
| | 2A) PLEASE PROVIDE YOUR MINIMUM BUILDING DESIGN NOT OR |
| | IA OR IB. 2010 FBC-B TABLE 503. |
| | |
| | 2BPLEASE CLARIFY IF THIS PERMIT IS FOR ONE BUILDING |
| | WITH 2 WINGS OR IF THIS PERIMIT IS TO BE FOR 2 |
| | BUILDINGS WITH A CONNECTING CORRIDOR. UNDER THE HEADING |
| | PROJECT DESCRIPTION IT IS LISTED AS (2) 5 STORY |
| | BUILDINGS. PLEASE NOTE THE HISTORIC BUILDING OR WING IS |
| | THE EST ONE THAT HAS TWO VERTICAL EXITS. THE WEST |
| | BUILDING OR WING ONLY HAS ONE VERTICAL EXIT. THE OTHER |
| | ISSUE THAT NEEDS TO BE REVIEWED, IS FBC-B 503.1.2 |
| | TWO BUILDINGS ON THE SAME LOT. IF THIS IS TO BE |
| | CONSIDERED ONE BUILDING THERE ARE NO FIRE SEPERATION |
| | ISSUES. IF THE DESIGN IS INTENDED TO BE TWO BUILDINGS |
| | WITH A CONNECTING CORRIDOR, SKY BRIDGE ETC.. THEN AN |
| | ASSUMED PROPERTY LINE HAS TO BE ASSIGNED AND BUILDING |
| | OPENINGS TO BE REVIEWED. |
| | |
| | 2C) THE EAST WING OR BUILDING IS LISTED AS A 5 STORY |
| | BUILDING, THE ROOF TOP IS INDICATED TO BE USED AS A |
| | ROOFTOP DECK WITH ROOF TRELLIS ABOVE, PLEASE REVIEW |
| | 2010 FBC-B 1509.2.3 PENTHOUSES OR BULKHEADS USED FOR |
| | PURPOSES OTHER THAN PERMITTED BY THIS SECTION SHALL |
| | CONFORM TO THE REQUIREMENTS OF THIS CODE FOR AN |
| | ADDITIONAL STORY OR A 6 STORY BUILDING. |
| | |
| | 2D)FOR HISTORIC BUILDINGS THERE ARE VARIOUS METHODS OF |
| | ACHIEVING CODE COMPLIANCE, 2010 EXISITNG BUILDING CODE |
| | CHAPTER 11, PLEASE PICK ONE: |
| | 1105.1 STRICT COMPLIANCE. |
| | 1105.2 COMPLIANCE OPTION |
| | 1105.3 CONDITIONS SPECIFIC TO COMPLIANCE OPTIONS 2 & 3. |
| | ALSO SEE 1104.1 EQUIVALENCY. |
| | |
| | 2E) THE BUILDING IS BEING DECLARED AS A LEVEL 3 |
| | ALTERATION. THE 2010 FL EXISTING BUILDING CODE804.1. |
| | AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED IN ALL |
| | WORK AREAS IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. FBC-B [F] 903.2.11.3 BUILDINGS THREE |
| | STORIES OR MORE IN HEIGHT. ANY BUILDING WHICH IS OF |
| | THREE STORIES OR MORE IN HEIGHT SHALL BE EQUIPPED WITH |
| | AN APPROVED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.1. |
| | |
| | 3) SHEET A.01 INDEX: |
| | 3A) MISSING LIFE-SAFETY SHEETS. WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRTION, 2010 EDITION 107.3.5.1.1 COMMERCIAL |
| | BUILDINGS 7. |
| | |
| | 3B) TYPO INDEX INDICATES A A2.11 MISSING BUT LABLEED |
| | A2.12. |
| | |
| | 4) SITE PLAN: |
| | 4A) POOL AND POOL DECK WILL REQUIRE A SEPERATE PERMIT. |
| | , NOTE ALDO COMPLIANCE WITH EFFECTIVE BARRIER A 48 " |
| | HIGH FENCE SEPERATING THE POOL AREA FROM TTHE REMAINDER |
| | OF THE BUILDING. FBC-B 424.1.3.1.9. |
| | |
| | 4B) UNKNOWN AREA, ARROWS PONTING AT BUT NO |
| | NOMENCLATURE, SEE SHEET A2.0 BETWWEN GRID LINES AB & AC |
| | AND ABOVE A1? 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 4C) CHANGE IN GRADE IS GIVEN FOR LOBBY BUT NOT FOR THE |
| | GARAGE TO THE PARKING LOBBY ENTRANCE NOR FROM THE |
| | PARKING GARAGE ENTRY TO THE SOUTH PARKING LOT. |
| | 107.2.1.3 ADDITIONAL INFORMATION REQUIRED, |
| | PLEASE SEE FBC-B 1003.5. |
| | |
| | 5) SHEET A2.0A: COMMON SATEMENT TO ALL FLOORS!!! |
| | 5A) WALL IDENTIFICATION TAGS MISSING, IDENTIFYING WALL |
| | CONSTRUCTION TYPES, FIRE BARRIERS, SHAFT ENCLOSURES AND |
| | TENANT SEPERATION WALLS. |
| | 2 HOUR SHAFT WALLS FOR ENCLOSED STAIRS AND SHAFTS. |
| | FBC-B 708.2. NO SHAFTS ARE LABELED AS SUCH. |
| | 2 HOUR SHAFT WALL CONSTRUCTION FOR TRASH CHUTE |
| | CONSTRUCTION FBC-B 708.13.1 PROVIDE A SECTION THROUGH |
| | THE ROOM, TRASH CHUTE AND 2 HOUR WALL, SEE FBC-B |
| | 903.2.11.2. RUBBISH CHUTES |
| | 2 HR ELEVATOR MACHINE ROOM FBC-B 3006.4. |
| | 1 HR TENANT SEPERATION WALLS FBC-B 709.1. |
| | 1 HR TERMINATION ROOM FOR TRASH CHUTE FBC-B 708.13.4. & |
| | OPENING PROTECTIVES IN ACCORDANCE WITH FBC-B TABLE |
| | 715.4 NOTE MECHANICAL SHOW EAST TERMINATION ROOM WITH |
| | FULL LOUVERED DOOR |
| | 1 HR REFUGE CHUTE ACCESS ROOMS FBC-B 708.13.3. & |
| | OPENING PROTECTIVES IN ACCORDANCE WITH FBC-B TABLE |
| | 715.4 |
| | |
| | TABLE FBC-B TABLE 508.4 NON- SPRINKLERED BUSINESS OCC |
| | OR ASSEMBLY VERSES R2 OCCUPANCY, 2 HOUR. |
| | FIRE PUMP ROOM (IF PROVIDED, NOT A HIGH-RISE) 2 HRS. |
| | FBC-B 913.2.1 |
| | GENERATOR ROOM 2 HR WALLS (IFPROVIDED, NOT A HIGH-RISE) |
| | NFPA 20:5.1.2.1.1. |
| | |
| | 5B) DOORS ARE NOT IDENTIFIED, THE DOOR SCHEDULE FOUND |
| | ON SHEET A6.0 DOES NOT INDICATE ANY FIRE RATINGS, DOORS |
| | LISTED IN WALLS TYPES ABOVE WILL NEED OPENING |
| | PROTECTION IN ACCORDANCE WITH FBC-B TABLE 715.4. |
| | |
| | 5C) LOBBY HANDRAIL PROVIDE THE DISTANCE BETWEEN WALLS |
| | AND HANDRAILS, FBC-B 1012.9 INTERMEDIATE HANDRAILS, |
| | RAMPS AND STAIRS AT WALL LINE DO NOT INDICATE THE USE |
| | OF HANDRAILS FBC-B 1009.12 & 1010.8. |
| | |
| | 5D) LOBBY STAIR, PLEASE REVIEW FBC-B 1003.5 EXCEPTION # |
| | 2 AND STIAR TREAD OF 13 INCHES. |
| | |
| | 5E) WALLS BETWEEN COMMON AREAS, CORRIDORS AND TENANT |
| | WALLS WILL ALSO NEED DOCUMENTATION THEY MEET SECTION |
| | FBC-B 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 5F) PLEASE CONFIRM THE ELEVATOR LOCATED IN GRID LINES |
| | B4 & BD IS NEW CONSTRUCTION, THE STRUCTURAL SHEETS SHOW |
| | WORK IN THIS AREA ON ALL FLOORS, IF SO PLEASE ALSO |
| | REVIEW 3002.4 ELEVATOR AMBULANCE STRETCHER |
| | REQUIREMENTS. |
| | |
| | 6) SHEET A2.1A, COMMON NOTE FOR ALL FLOORS: |
| | 6A) PLEASE PROVIDE COMPLIANCE WITH: |
| | FBC-B 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE |
| | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF |
| | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 492. |
| | |
| | 6B) FBC-B 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | EXCEPTIONS: |
| | 1. FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | 2. FLOOR INSULATION INSTALLED BETWEEN A FINISHED FLOOR |
| | AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | 6C) THE 2 STORY UNITS DO NOT PROVIDE DETAILS OF THE NEW |
| | INTERIOR STAIRS AS TO LIVE LOADS, TABLE 1607.1 OR |
| | COMPLIANCE WITH 1009.6 STAIRWAY CONSTRUCTION. ALL |
| | STAIRWAYS SHALL BE BUILT OF MATERIALS CONSISTENT WITH |
| | THE TYPES PERMITTED FOR THE TYPE OF CONSTRUCTION OF THE |
| | BUILDING, EXCEPT THAT WOOD HANDRAILS SHALL BE PERMITTED |
| | FOR ALL TYPES OF CONSTRUCTION. |
| | |
| | 6D) DETAIL A2-4.1 CUT THROUGH SECTION NO DETAILS FOR |
| | GAURDRAIL ON BALCONY. TO COMPLY WITH FBC-B SECTION |
| | 1013., 1607.7.1, 1607.7.1.1 & 1607.7.1.2. |
| | |
| | 7) SHEET A2.5 ROOF DECK: |
| | 7A) THE ROOF DECK IS BEING USED FOR MORE THAN A ROOF |
| | DECK, THE USEAGE OF THIS AREA MAKES THE ROOF DECK A 6TH |
| | FLOOR, SEE FBC-B 1509.2.3 USE LIMITATIONS. PENTHOUSES |
| | OR BULKHEADS USED FOR PURPOSES OTHER THAN PERMITTED BY |
| | THIS SECTION SHALL CONFORM TO THE REQUIREMENTS OF THIS |
| | CODE FOR AN ADDITIONAL STORY. THE RESTRICTIONS OF THIS |
| | SECTION SHALL NOT PROHIBIT THE PLACING OF WOOD |
| | FLAGPOLES OR SIMILAR STRUCTURES ON THE ROOF OF ANY |
| | BUILDING. |
| | |
| | 7B) FBC-B 1509.2.4 TYPE OF CONSTRUCTION. |
| | PENTHOUSES SHALL BE CONSTRUCTED WITH WALLS, FLOORS AND |
| | ROOF AS REQUIRED FOR THE BUILDING. |
| | |
| | 7C) THIS PLAN INDICATES ONLY ONE MEANS OF EGRESS, |
| | PLEASE REVIEW FBC-B TABLE 1021.2 STORIES WITH ONE EXIT. |
| | |
| | 8) SHEET A-5.0: |
| | 8A) EYEBROW SUNSHADE BY DORALCO OR APPROVED EQUAL. WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH INFORMATION |
| | SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" |
| | OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION... |
| | |
| | 8B) DETAIL # 2 POOL RETAINING WALL INDICATES A |
| | POOLPAVER DECK BUT THE SUB-BASE IS NOT PROVIDED, |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED, TO BE |
| | UNDER SEPERATE PERMIT. |
| | |
| | 8C) DETAIL # 3 FIRE STOPPING MATERIALS AS REQUIRED FOR |
| | FIRE RATING, WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION... |
| | |
| | 8D) DETAIL #4, INDICATES WINDOWS BY E. S. WINDOWS OR |
| | EQUAL, WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION... |
| | |
| | 9 SHEET S-1.0 WIND DESIGN IS INDICATED TO BE A EXPOSURE |
| | C, PLEASE SEE FBC-B 1609.4 EXPOSURE CATEGORY.EXPOSURE |
| | D. EXPOSURE D SHALL APPLY WHERE THE GROUND SURFACE |
| | ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, PREVAILS |
| | IN THE UPWIND DIRECTION FOR A DISTANCE OF AT LEAST |
| | 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE |
| | BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL EXTEND |
| | INLAND FROM THE SHORELINE FOR A DISTANCE OF 600 FEET |
| | (183 M) OR 20 TIMES THE HEIGHT OF THE BUILDING, |
| | WHICHEVER IS GREATER FROM AN EXPOSURE D CONDITION AS |
| | DEFINED IN THE PREVIOUS SENTENCE. |
| | |
| | 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 11) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | . |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |