Plan Review Notes
Plan Review Notes For Permit 13081230
Permit Number 13081230
Review Stop B
Sequence Number 1
Notes
Date Text
2013-09-23 15:08:25BUILDING PLAN REVIEW
 PERMIT:13081230
 ADD: 300 PALM BEACH LAKES
 CONT: DALL CONSRUCTION CO
 TEL: (305)458-8314
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 9/23/2013
 ACTION: DENIED
  
 THE PLANS SUBMITTED ARE MORE OF A RENDERING THAN
 BUILDABLE SET OF PLANS PLEASE BE AWARE A THOROUGH
 REVIEW CAN NOT BE MADE AT THIS TIME, AS A RESULT OF THE
 ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS
 MAY APPEAR THAT WERE NOT PART OF THIS REVIEW.'
 1) THIS BUILDING MEETS THE DEFINITION OF A THRESHOLD
 BUILDING. THRESHOLD INSPECTION PLAN FL S. S. 553.71(7)
 " THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION AND FORMS BEFORE THE PERMIT MAY BE
 ISSUED.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 109.3.6.4.4
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 1D) A PLAN REVIEW STOP (THRESHOLD) WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD: PLEASE CALL
 THE CITY OF WEST PALM BEACH'S AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR IN-PROGRESS
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 1F) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 1G) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 1H) THREE SETS OF PLANS AND PRODUCT TESTING REPORTS
 WILL BE REQUIRED, SINCE THIS IS A THRESHOLD BUILDING.
  
 2) SHEET A0.0 PROJECT DATA:
 2A) PLEASE PROVIDE YOUR MINIMUM BUILDING DESIGN NOT OR
 IA OR IB. 2010 FBC-B TABLE 503.
  
 2BPLEASE CLARIFY IF THIS PERMIT IS FOR ONE BUILDING
 WITH 2 WINGS OR IF THIS PERIMIT IS TO BE FOR 2
 BUILDINGS WITH A CONNECTING CORRIDOR. UNDER THE HEADING
 PROJECT DESCRIPTION IT IS LISTED AS (2) 5 STORY
 BUILDINGS. PLEASE NOTE THE HISTORIC BUILDING OR WING IS
 THE EST ONE THAT HAS TWO VERTICAL EXITS. THE WEST
 BUILDING OR WING ONLY HAS ONE VERTICAL EXIT. THE OTHER
 ISSUE THAT NEEDS TO BE REVIEWED, IS FBC-B 503.1.2
 TWO BUILDINGS ON THE SAME LOT. IF THIS IS TO BE
 CONSIDERED ONE BUILDING THERE ARE NO FIRE SEPERATION
 ISSUES. IF THE DESIGN IS INTENDED TO BE TWO BUILDINGS
 WITH A CONNECTING CORRIDOR, SKY BRIDGE ETC.. THEN AN
 ASSUMED PROPERTY LINE HAS TO BE ASSIGNED AND BUILDING
 OPENINGS TO BE REVIEWED.
  
 2C) THE EAST WING OR BUILDING IS LISTED AS A 5 STORY
 BUILDING, THE ROOF TOP IS INDICATED TO BE USED AS A
 ROOFTOP DECK WITH ROOF TRELLIS ABOVE, PLEASE REVIEW
 2010 FBC-B 1509.2.3 PENTHOUSES OR BULKHEADS USED FOR
 PURPOSES OTHER THAN PERMITTED BY THIS SECTION SHALL
 CONFORM TO THE REQUIREMENTS OF THIS CODE FOR AN
 ADDITIONAL STORY OR A 6 STORY BUILDING.
  
 2D)FOR HISTORIC BUILDINGS THERE ARE VARIOUS METHODS OF
 ACHIEVING CODE COMPLIANCE, 2010 EXISITNG BUILDING CODE
 CHAPTER 11, PLEASE PICK ONE:
 1105.1 STRICT COMPLIANCE.
 1105.2 COMPLIANCE OPTION
 1105.3 CONDITIONS SPECIFIC TO COMPLIANCE OPTIONS 2 & 3.
 ALSO SEE 1104.1 EQUIVALENCY.
  
 2E) THE BUILDING IS BEING DECLARED AS A LEVEL 3
 ALTERATION. THE 2010 FL EXISTING BUILDING CODE804.1.
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED IN ALL
 WORK AREAS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING. FBC-B [F] 903.2.11.3 BUILDINGS THREE
 STORIES OR MORE IN HEIGHT. ANY BUILDING WHICH IS OF
 THREE STORIES OR MORE IN HEIGHT SHALL BE EQUIPPED WITH
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH SECTION 903.1.
  
 3) SHEET A.01 INDEX:
 3A) MISSING LIFE-SAFETY SHEETS. WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRTION, 2010 EDITION 107.3.5.1.1 COMMERCIAL
 BUILDINGS 7.
  
 3B) TYPO INDEX INDICATES A A2.11 MISSING BUT LABLEED
 A2.12.
  
 4) SITE PLAN:
 4A) POOL AND POOL DECK WILL REQUIRE A SEPERATE PERMIT.
 , NOTE ALDO COMPLIANCE WITH EFFECTIVE BARRIER A 48 "
 HIGH FENCE SEPERATING THE POOL AREA FROM TTHE REMAINDER
 OF THE BUILDING. FBC-B 424.1.3.1.9.
  
 4B) UNKNOWN AREA, ARROWS PONTING AT BUT NO
 NOMENCLATURE, SEE SHEET A2.0 BETWWEN GRID LINES AB & AC
 AND ABOVE A1? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4C) CHANGE IN GRADE IS GIVEN FOR LOBBY BUT NOT FOR THE
 GARAGE TO THE PARKING LOBBY ENTRANCE NOR FROM THE
 PARKING GARAGE ENTRY TO THE SOUTH PARKING LOT.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED,
 PLEASE SEE FBC-B 1003.5.
  
 5) SHEET A2.0A: COMMON SATEMENT TO ALL FLOORS!!!
 5A) WALL IDENTIFICATION TAGS MISSING, IDENTIFYING WALL
 CONSTRUCTION TYPES, FIRE BARRIERS, SHAFT ENCLOSURES AND
 TENANT SEPERATION WALLS.
 2 HOUR SHAFT WALLS FOR ENCLOSED STAIRS AND SHAFTS.
 FBC-B 708.2. NO SHAFTS ARE LABELED AS SUCH.
 2 HOUR SHAFT WALL CONSTRUCTION FOR TRASH CHUTE
 CONSTRUCTION FBC-B 708.13.1 PROVIDE A SECTION THROUGH
 THE ROOM, TRASH CHUTE AND 2 HOUR WALL, SEE FBC-B
 903.2.11.2. RUBBISH CHUTES
 2 HR ELEVATOR MACHINE ROOM FBC-B 3006.4.
 1 HR TENANT SEPERATION WALLS FBC-B 709.1.
 1 HR TERMINATION ROOM FOR TRASH CHUTE FBC-B 708.13.4. &
 OPENING PROTECTIVES IN ACCORDANCE WITH FBC-B TABLE
 715.4 NOTE MECHANICAL SHOW EAST TERMINATION ROOM WITH
 FULL LOUVERED DOOR
 1 HR REFUGE CHUTE ACCESS ROOMS FBC-B 708.13.3. &
 OPENING PROTECTIVES IN ACCORDANCE WITH FBC-B TABLE
 715.4
  
 TABLE FBC-B TABLE 508.4 NON- SPRINKLERED BUSINESS OCC
 OR ASSEMBLY VERSES R2 OCCUPANCY, 2 HOUR.
 FIRE PUMP ROOM (IF PROVIDED, NOT A HIGH-RISE) 2 HRS.
 FBC-B 913.2.1
 GENERATOR ROOM 2 HR WALLS (IFPROVIDED, NOT A HIGH-RISE)
 NFPA 20:5.1.2.1.1.
  
 5B) DOORS ARE NOT IDENTIFIED, THE DOOR SCHEDULE FOUND
 ON SHEET A6.0 DOES NOT INDICATE ANY FIRE RATINGS, DOORS
 LISTED IN WALLS TYPES ABOVE WILL NEED OPENING
 PROTECTION IN ACCORDANCE WITH FBC-B TABLE 715.4.
  
 5C) LOBBY HANDRAIL PROVIDE THE DISTANCE BETWEEN WALLS
 AND HANDRAILS, FBC-B 1012.9 INTERMEDIATE HANDRAILS,
 RAMPS AND STAIRS AT WALL LINE DO NOT INDICATE THE USE
 OF HANDRAILS FBC-B 1009.12 & 1010.8.
  
 5D) LOBBY STAIR, PLEASE REVIEW FBC-B 1003.5 EXCEPTION #
 2 AND STIAR TREAD OF 13 INCHES.
  
 5E) WALLS BETWEEN COMMON AREAS, CORRIDORS AND TENANT
 WALLS WILL ALSO NEED DOCUMENTATION THEY MEET SECTION
 FBC-B 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 5F) PLEASE CONFIRM THE ELEVATOR LOCATED IN GRID LINES
 B4 & BD IS NEW CONSTRUCTION, THE STRUCTURAL SHEETS SHOW
 WORK IN THIS AREA ON ALL FLOORS, IF SO PLEASE ALSO
 REVIEW 3002.4 ELEVATOR AMBULANCE STRETCHER
 REQUIREMENTS.
  
 6) SHEET A2.1A, COMMON NOTE FOR ALL FLOORS:
 6A) PLEASE PROVIDE COMPLIANCE WITH:
 FBC-B 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 6B) FBC-B 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 EXCEPTIONS:
 1. FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. FLOOR INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 6C) THE 2 STORY UNITS DO NOT PROVIDE DETAILS OF THE NEW
 INTERIOR STAIRS AS TO LIVE LOADS, TABLE 1607.1 OR
 COMPLIANCE WITH 1009.6 STAIRWAY CONSTRUCTION. ALL
 STAIRWAYS SHALL BE BUILT OF MATERIALS CONSISTENT WITH
 THE TYPES PERMITTED FOR THE TYPE OF CONSTRUCTION OF THE
 BUILDING, EXCEPT THAT WOOD HANDRAILS SHALL BE PERMITTED
 FOR ALL TYPES OF CONSTRUCTION.
  
 6D) DETAIL A2-4.1 CUT THROUGH SECTION NO DETAILS FOR
 GAURDRAIL ON BALCONY. TO COMPLY WITH FBC-B SECTION
 1013., 1607.7.1, 1607.7.1.1 & 1607.7.1.2.
  
 7) SHEET A2.5 ROOF DECK:
 7A) THE ROOF DECK IS BEING USED FOR MORE THAN A ROOF
 DECK, THE USEAGE OF THIS AREA MAKES THE ROOF DECK A 6TH
 FLOOR, SEE FBC-B 1509.2.3 USE LIMITATIONS. PENTHOUSES
 OR BULKHEADS USED FOR PURPOSES OTHER THAN PERMITTED BY
 THIS SECTION SHALL CONFORM TO THE REQUIREMENTS OF THIS
 CODE FOR AN ADDITIONAL STORY. THE RESTRICTIONS OF THIS
 SECTION SHALL NOT PROHIBIT THE PLACING OF WOOD
 FLAGPOLES OR SIMILAR STRUCTURES ON THE ROOF OF ANY
 BUILDING.
  
 7B) FBC-B 1509.2.4 TYPE OF CONSTRUCTION.
 PENTHOUSES SHALL BE CONSTRUCTED WITH WALLS, FLOORS AND
 ROOF AS REQUIRED FOR THE BUILDING.
  
 7C) THIS PLAN INDICATES ONLY ONE MEANS OF EGRESS,
 PLEASE REVIEW FBC-B TABLE 1021.2 STORIES WITH ONE EXIT.
  
 8) SHEET A-5.0:
 8A) EYEBROW SUNSHADE BY DORALCO OR APPROVED EQUAL. WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH INFORMATION
 SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL"
 OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION...
  
 8B) DETAIL # 2 POOL RETAINING WALL INDICATES A
 POOLPAVER DECK BUT THE SUB-BASE IS NOT PROVIDED,
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED, TO BE
 UNDER SEPERATE PERMIT.
  
 8C) DETAIL # 3 FIRE STOPPING MATERIALS AS REQUIRED FOR
 FIRE RATING, WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION...
  
 8D) DETAIL #4, INDICATES WINDOWS BY E. S. WINDOWS OR
 EQUAL, WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION...
  
 9 SHEET S-1.0 WIND DESIGN IS INDICATED TO BE A EXPOSURE
 C, PLEASE SEE FBC-B 1609.4 EXPOSURE CATEGORY.EXPOSURE
 D. EXPOSURE D SHALL APPLY WHERE THE GROUND SURFACE
 ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, PREVAILS
 IN THE UPWIND DIRECTION FOR A DISTANCE OF AT LEAST
 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL EXTEND
 INLAND FROM THE SHORELINE FOR A DISTANCE OF 600 FEET
 (183 M) OR 20 TIMES THE HEIGHT OF THE BUILDING,
 WHICHEVER IS GREATER FROM AN EXPOSURE D CONDITION AS
 DEFINED IN THE PREVIOUS SENTENCE.
  
 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  