| Plan Review Notes For Permit 13081204 |
| Permit Number |
13081204 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-11 10:04:21 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | A NEW AIR HANDLER AND CONDENSER UNIT ARE SHOWN ON THE | | | PLANS. | | | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS IN | | | ACCORDANCE WITH ACCA MANUAL J FOR THE HVAC EQUIPMENT. | | | FBCR M1401.3 | | | | | | 2) SUBMIT TWO SETS OF MECHANICAL PLANS. FBCR M1601.1 | | | SHOW THE DUCT LOCATION AND SIZE. SPECIFY THE SUPPLY | | | GRILL SIZES AND CFMS AT EACH DROP. SPECIFY THE RETURN | | | LOCATIONS, DUCT AND GRILL SIZES AND SHOW COMPLIANCE | | | WITH FBC M1602.4 FOR BALANCED RETURN AIR. | | | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | | PLANS. | | | | | | 4) PROVIDE AN ANCHORING DETAIL CAPABLE OF RESISTING THE | | | APPLICABLE WIND PRESSURES FOR THE EXTERIOR EQUIPMENT. | | | FBCR M1307.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|