| Plan Review Notes For Permit 13081204 |
| Permit Number |
13081204 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-11 11:04:32 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) PROVIDE THE TOTAL LOAD CALCULATIONS FOR THE EXISTING | | | POOL CABANA AND THE ADDITION. NEC 220.83 (B) AND CITY | | | AMENDMENTS 107.3.5.3 | | | | | | 2) PROVIDE A PANEL SCHEDULE FOR THE 100 AMP PANEL | | | SERVICING THE POOL CABANA. NEC 408.4 AND CITY | | | AMENDMENTS 107.3.5.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|