| Plan Review Notes For Permit 13081195 |
| Permit Number |
13081195 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-17 12:07:01 | THE FOLLOW ADDITIONS NEED TO BE SUBMITTED TO PROPERLY | | | COMPLETE THE ELECTRICAL PLAN REVIEW: | | | 1. THE RISER DIAGRAM SIMPLY INDICATES THE CONDUCTOR | | | SIZE AND QUANTITY ALONG WITH THE CORRESPONDING RACEWAY | | | A) IN ADDITION TO THAT I WOULD NEED TO SHOW CONDUCTOR | | | TYPE AND INSULATION ALONG WITH THE LENGTH OF THE RUNS. | | | 2. THE PANEL SCHEDULES INDICATE A RATING AND OCPD WHERE | | | APPLICABLE, | | | A) IN ADDITION TO THE RATING & OCPD, I NEED TO SEE LOAD | | | CALCS TO SEE THE CONNECTED LOADS | | | | | | SENT BACK TO BIN WHILE WAITING FOR CORRECTIONS BY: MA. | | | |
|