Plan Review Notes
Plan Review Notes For Permit 13081177
Permit Number 13081177
Review Stop B
Sequence Number 1
Notes
Date Text
2013-09-14 10:13:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS FBC
 RESIDENTIAL 310, EXISTING BUIDLING 604.1.
  
 2. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING
 INFORMATION ***FOR BEDROOMS/SLEEPING ROOMS ONLY***; FBC
 R310, FBC EB 604.1. THE CLEAR OPENING CANNOT BE REDUCED
 BY MORE THAN 5%:
  
 REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW
 IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG?
  
 REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER.
  
 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FAC9N-3. THE PRODUCT APPROVAL SUBMITTED IS FOR
 MULLIONS. SOME DOOR CUT SHEETS WERE PROVIDED, BUT DOORS
 ARE NOT IN THE SCOPE OF THIS APPLICATION.
  
 IF PRODUCT APPROVAL TO BE SUBMITTED FOR WINDOWS IS NOT
 A MIAMIDADE NOA, PRODUCT APPROVAL TO INCLUDE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEET
 (WWW.FLORIDABUILDING.ORG), EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS.
  
  
  