2013-08-29 19:32:35COMMERCIAL REROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 13-0129.15 SUBMITTED. NEED THE RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES REQUIRED BY SEC. 1609.4.3 OF
 2010 FBC.
  
 ***NOTE: THIS BUILDING IS LOCATED IN EXPOSURE "C".
  