| Notes |
| Date |
Text |
| 2013-09-09 13:26:01 | PROVIDE RISER DIAGRAM/ONE LINE DRAWING SHOWING | | | ELECTRICAL EQUIPMENT | | | INDICATE LOADS PER NEC 210 AND 220 | | | PROVIDE MOTOR CALCULATIONS PER NEC 430, INCLUDING | | | DISCONNECTS PER 430.102 | | | PROVIDE OVERLOAD PROTECTION OR INDICATE IF MOTOR IS | | | INTERNALLY OVERLOAD PROTECTED 430.32 | | | PROVIDE RATING OF MOTOR AND DRIVEN MACHINERY TO ENSURE | | | COMPATIBILITY | | | EDISON BASE FUSES ARE FOR REPLACEMENT ONLY - 240.51 |
|