| Plan Review Notes For Permit 13081099 |
| Permit Number |
13081099 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-16 11:15:57 | THE FOLLOWING ITEMS SHALL BE ADDRESSED FOR A SUCCESSFUL | | | ELECTRICAL PLANS REVIEW: | | | 1. PROVIDE AN ELECTRICAL RISER DIAGRAM SHOWING PROPER | | | WIRE SIZE AND GROUNDING. | | | 2. INDICATE ON THE DRAWINGS THE LOCATION OF BOTH, THE | | | ELECTRIC METER AND THE ELECTRICAL PANEL. | | | 3. INCLUDE ON THE DRAWING THE LOCATION OF THE REQUIRED | | | SMOKE DETECTORS. | | | 4. THE ELECTRICAL LOAD CALCS DUE SHOW A DRYER, BUT THEY | | | FAIL TO SHOW THE WASHER CIRCUIT OR LOAD. | | | 5. SHOW THE LOCATION OF THE WASHER & DRYER ON THE PLANS | | | 6. LOAD CALCS INDICATE THE LOAD AND CIRCUIT FOUR THE | | | WATER HEATER BUT THE LOCATION OF SAME IS NOT ON THE | | | PLANS. | | | 7. NEC 210.52, REQUIRES THAT EVERY USABLE WALL SPACE | | | GREATER THEN 24" HAVE AN ELECTRICAL OUTLET. | | | | | | SENT BACK TO BIN WAITING FOR CORRECTIONS BY: MA |
|