| Plan Review Notes For Permit 13081049 |
| Permit Number |
13081049 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-10-21 17:19:43 | PROVISO: | | | TENANT SEPERATION WALL IS ALSSO A OCCUPANCY SEPERATION | | | WALL. | | | WILL REQUIRE 2 HR FIRE SEPERATION IF BUILDING IS NOT | | | FIRE SPRINKLERED. | | | WILL REQUIRE 1 HR FIRE SEPERATION IF BUILDING IS FIRE | | | SPRINKLERED. | | | 2010 FBC-B TABLE 508.4. | | | | | | NEW FTOREFRONT DOOR REQUIRES STORM SHUTTERS UNDER | | | SEPERATE PERMIT. | | | 2010 FBC-B 1609.1.2/ 1609.4.4.1 | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|