2013-09-11 17:52:37871 VILLAGE BOULEVARD - #602A
 PERMIT #13081049
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: THE ADDRESS PROVIDED ON THE PLANS (721 VILLAGE
 BOULEVARD) DOES NOT MATCH THE ADDRESS PROVIDED ON THE
 PERMIT APPLICATION (871 VILLAGE BOULEVARD). ALSO, NO
 SUITE NUMBER PROVIDED ON THE PLANS.
  
 GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 GENERAL: CONFIRM EXISTING DOORS ARE EQUIPPED WITH PANIC
 HARDWARE.
  
 GENERAL: PROVIDE A SEATING LAYOUT.
  
 SHEET E2: NO EMERGENCY LIGHTING PROVIDED. EMERGENCY
 ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM OF 1.5
 HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING.
 EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO
 PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN
 AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN
 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT
 FLOOR LEVEL.
  
 SHEET E2: NO EXIT SIGNS PROVIDED FOR REAR EGRESS OR
 EXIT.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]