| Date |
Text |
| 2013-09-11 17:52:37 | 871 VILLAGE BOULEVARD - #602A |
| | PERMIT #13081049 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: THE ADDRESS PROVIDED ON THE PLANS (721 VILLAGE |
| | BOULEVARD) DOES NOT MATCH THE ADDRESS PROVIDED ON THE |
| | PERMIT APPLICATION (871 VILLAGE BOULEVARD). ALSO, NO |
| | SUITE NUMBER PROVIDED ON THE PLANS. |
| | |
| | GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED |
| | SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED |
| | IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE |
| | ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | GENERAL: CONFIRM EXISTING DOORS ARE EQUIPPED WITH PANIC |
| | HARDWARE. |
| | |
| | GENERAL: PROVIDE A SEATING LAYOUT. |
| | |
| | SHEET E2: NO EMERGENCY LIGHTING PROVIDED. EMERGENCY |
| | ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM OF 1.5 |
| | HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING. |
| | EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO |
| | PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN |
| | AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN |
| | 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT |
| | FLOOR LEVEL. |
| | |
| | SHEET E2: NO EXIT SIGNS PROVIDED FOR REAR EGRESS OR |
| | EXIT. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |