| Plan Review Notes For Permit 13081049 |
| Permit Number |
13081049 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-11 10:12:44 | SHEET E3 | | | 1) EXSTING SERVICE IS RATED FOR 200 AMPS. HOWEVER, THE | | | DEMANS LOAD SHOW 203 AMPS. NEED TO TAKE INTO ACCOUNT | | | CONTINUOUS LOADS, | | | 2) PROVIDE THE SERVICE CONDUCTOR INSULATION TYPE, SIZE, | | | LENGTH AND MATERIAL. FBC 107.3.5. | | | 3) PROVIDE THE SIZE OF THE SERVICE CONDUCTOR CONDUIT | | | TYPE AND SIZE. FBC 107.3.5. | | | 4) NEED TO COMPLY WITH FBC ENERGY CONSERVATION CODE | | | SECTION 505.7.3. | | | 5) PROVIDE SIZE OF CONDUIT AND CONDUCTORS SIZE FOR EACH | | | NEW BRANCH CIRCUITS. | | | SHEET E2 | | | 1) ADDITIONAL EXIT LIGHT IS REQUIRED AT REAR DOOR. | | | PROVIDE BRANCH CIRCUIT. | | | 2) EMERGENCY LIGHTING IS REQUIRED. NEED TO COMPLY WITH | | | FBC 1006.2 FOR LIGHTING DENSIITY. | | | | | | REVIEWED BY WDS. | | | DENIED IN (I) |
|