Plan Review Notes
Plan Review Notes For Permit 13081049
Permit Number 13081049
Review Stop E
Sequence Number 1
Notes
Date Text
2013-10-11 10:12:44SHEET E3
 1) EXSTING SERVICE IS RATED FOR 200 AMPS. HOWEVER, THE
 DEMANS LOAD SHOW 203 AMPS. NEED TO TAKE INTO ACCOUNT
 CONTINUOUS LOADS,
 2) PROVIDE THE SERVICE CONDUCTOR INSULATION TYPE, SIZE,
 LENGTH AND MATERIAL. FBC 107.3.5.
 3) PROVIDE THE SIZE OF THE SERVICE CONDUCTOR CONDUIT
 TYPE AND SIZE. FBC 107.3.5.
 4) NEED TO COMPLY WITH FBC ENERGY CONSERVATION CODE
 SECTION 505.7.3.
 5) PROVIDE SIZE OF CONDUIT AND CONDUCTORS SIZE FOR EACH
 NEW BRANCH CIRCUITS.
 SHEET E2
 1) ADDITIONAL EXIT LIGHT IS REQUIRED AT REAR DOOR.
 PROVIDE BRANCH CIRCUIT.
 2) EMERGENCY LIGHTING IS REQUIRED. NEED TO COMPLY WITH
 FBC 1006.2 FOR LIGHTING DENSIITY.
  
 REVIEWED BY WDS.
 DENIED IN (I)