Plan Review Notes
Plan Review Notes For Permit 13081031
Permit Number 13081031
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-08-28 15:40:347001 PARKER AVE
 PERMIT # 13081031
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION.
 2. UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION
 OF THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS
 3.TEMPORARY BUILDING SHALL BE SEPARATED FROM ADJACENT
 STRUCTURE IN ACCORDANCE WITH NFPA 241, TABLE 4.2.1.
 CURRENT PLAN SHOWS EXPOSED SIDE TO BE 56 FEET AND A
 MINIMUM DISTANCE OF 50 FEET IS REQUIRED.
 4. PROVIDE LOCATION OF PORTABLE FIRE EXTINGUISHERS.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved