| Plan Review Notes For Permit 13080997 |
| Permit Number |
13080997 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-04 13:37:23 | FIRST REVIEW -9-4-13 | | | 1.PROVIDE PANEL SCHEDULE PER NEC 408.4 | | | 2. ALL NEW OUTLETS TO BE TAMPER RESISTANT AND AFCI | | | PROTECTED PER NEC 406.11 AND 210.12B | | | 3. SHOW CIRCUITRY AND ROOM NAMES FOR CLARITY ON | | | ELECTRICAL PLANS | | | 4. PROVIDE LOAD CALCS WITH ALL ADDITIONAL APPLIANCES, | | | FIXTURES AND CIRCUITS PER NEC 220 | | | 5. PROVIDE SMOKE ALARMS PER FLORIDA RESIDENTIAL CODE | | | SECTION 314 IF NOT ALREADY EXISTING | | | END OF REVIEW - VB | | | |
|