Plan Review Notes
Plan Review Notes For Permit 13080981
Permit Number 13080981
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-09-03 11:21:49316-322 BANYAN BOULEVARD
 PERMIT #13080981
 MASTER #12100583
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE CURRENT (WITH 12 MONTHS) HYDRANT FLOW TEST DATA
 ON PLANS. HYDRAULIC CALUCLATIONS DO NOT INDICATE A DATE
 OR TIME OF FLOW TEST.
  
 PROVIDE DUAL INLET FIRE DEPARTMENT CONNECTION. PROVIDE
 LOCKING KNOX CAPS ON FIRE DEPARTMENT CONNECTION.
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 NO SPRINKLER PROTECTION PROVIDED IN THE UPPER CIRCULAR
 SKYLIGHT AREA. PER NFPA 13 SECTION 8.6.7 (CELING
 POCKETS) SPRINKLER PROTECTION SHALL BE PROVIDED UNLESS
 ALL OF THE FOLLOWING ARE MET:
 (1) THE TOTAL VOLUME OF THE UNPROTECTED CEILING POCKET
 DOES NOT EXCEED 1000 CUBIC FEET.
 (2) THE DEPTH OF THE UNPROTECTED POCKET DOES NOT EXCEED
 36-INCHES.
 (3) THE ENTIRE FLOOR UNDER THE UNPROTECTED CEILING
 POCKET IS PROTECTED BY THE SPRINKLERS AT THE LOWER
 CEILING ELEVATION.
 (4) EACH UNPROTECTED CEILING POCKET IS SEPARATED FROM
 ANY ADJACENT UNPROTECTED CEILING POCKET BY A MINIMUM 10
 FEETRIZONTAL DISTANCE.
 (5) THE UNPROTECTED CEILING POCKET IS CONSTRUCTED OF
 NONCOMBUSTIBLE OR LIMITED COMBUSTIBLE CONSTRUCTION.
 (6) SKYLIGHTS NOT EXCEEDING 32 SQUARE FEET SHALL BE
 PERMITTED TO HAVE A PLASTIC COVER.
 (7) QUICK RESPONSE SPRINKLERS ARE UTILIZED THROUGHOUT
 THE COMPARTMENT.
  
 NOTE: SEPARATE UNDERGROUND FIRE LINE PERMIT NEEDED.
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION. SUBMIT PRODUCT DATA FOR BACKFLOW PREVENTER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  