| 2013-10-16 13:31:37 | THIS FILE HAS BEEN APPROVED WITH THE HEREIN DESCRIBED |
| | EXCEPTIONS WHICH SHALL BE BE REQUIRED FOR SUCCESSFUL |
| | INSPECTIONS. |
| | |
| | FROM THE PERMIT APPLICATION, I GATHER THAT THIS |
| | STRUCTURE WAS BUILT WITHOUT THE BENEFIT OF A PERMIT AND |
| | OR INSPECTIONS SOME TIME AGO. REGARDLESS OF THE TIME IT |
| | WAS BUILT, IT IS CURRENTLY BEING PERMITTED; THEREFORE |
| | IT SHALL COMPLY WITH CURRENT CODE REQUIREMENTS AS |
| | FOLLOWS: |
| | 1. THE ADDITION OF THIS ROOM MANDATES COMPLIANCE WITH |
| | THE FBCR 314. |
| | 2. THE ELECTRICAL CIRCUITS WITHING THE AREA IN QUESTION |
| | (WITHIN THE SCOPE OF THIS PERMIT) SHALL COMPLY WITH NEC |
| | 210.12 (B) AFCI |
| | 3. THE ELECTRICAL DEVICES WITH IN AREA IN QUESTION, |
| | SHALL COMPLY WITH NEC 406.11 WHICH REQUIRES |
| | TAMPER-RESISTANT OUTLETS. |
| | 4. THE LIGHT ON THE EXTERIOR OF THE ENTRY DOOR SHALL |
| | NOT BE BEHIND THE DOOR SWING. |
| | 5. THE SUBMITTED DRAWING DOES NOT INDICATE COMPLIANCE |
| | WITH NEC 210.52 WITH REGARDS TO PROPER OUTLET PLACING. |
| | FURTHERMORE, THE DEDICATED OUTLET FOR THE WALL A/C UNIT |
| | IS SHOWN TO BE 30 AMP AND THUS SHALL NOT BE CONSIDERED |
| | AS PART OF THE REQUIRED OULTELS ALONG THE WALL LINE, |
| | |
| | THOUGH SOME OR ALL OF THE ABOVE MENTIONED REQUIREMENTS |
| | MAY ALREADY BE IN PLACE, THEY ARE NOT REFLECTED ON THE |
| | SUBMITTED DRAWING AND THUS MENTIONED HEREIN. |
| | |
| | SENT BACK TO BIN FOR FURTHER REVIEWS BY: MA |
| | |
| | |