| Notes |
| Date |
Text |
| 2013-09-04 10:33:07 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | THE WATER CLOSETS ARE NOT PROPERLY VENTED AS SHOWN. WET | | | VENTING IS ONLY PERMITTED FOR UP TO TWO BATHROOMS AND | | | FOUR ARE SHOWN ON THE PLAN. CONNECTING EACH LAVATORY | | | STACK TO ITS ASSOCIATED WATER CLOSET BRANCH LINE, | | | CREATING FOUR WET VENTED RESTROOMS, WOULD BE OK. | | | 909.1 HORIZONTAL WET VENT PERMITTED. | | | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS | | | LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE | | | VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE | | | CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND | | | FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION | | | OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM | | | FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH | | | DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT | | | INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE | | | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO | | | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL | | | WET VENT. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|