2013-09-17 15:55:08FAILED
  
 1) THE PALM BEACH OUTLETS DESIGN GUIDELINES REQUIRE THE
 SCREENING OF THE ROOFTOP MECHANICAL EQUIPMENT.
  
 2) THE APPROVED ROOFTOP PLANS AND SITE LINE STUDY
 SHOWED NO RTU FOR THIS BAY. PROVIDE INFORMATION ON THE
 HEIGHT OF THE PROPOSED RTUS, INCLUDING THE 14" CURB AND
 THE DISTANCE OF THE UNITS TO THE SOUTHERR EDGE OF THE
 BUILDING.
  
 3) IF THE HEIGHT OF THE RTU PLUS THE CURB IS GREATER
 THAN 60 AND 7/8 INCHES OR CLOSER THAN 35 FEET TO THE
 SOUTHERN EDGE OF THE BUILDING, THEN A REVISED SIGHT
 LINE STUDY FOR THE NEW RTU, WHICH DEMONSTRATES THAT THE
 RTU IS SCREENED, SHALL BE PROVIDED WITH THE PERMIT
 RESUBMITTAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  