| 2013-09-17 13:36:03 | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. SHEETS P-1 & P-2: THE WATER CLOSET IN THE MENS ROOM |
| | IS NOT VENTED BY ONE OF THE METHODS IN CHAPTER 9. |
| | CONNECTING THE LAVATORY STACK TO THE WATER CLOSET |
| | BRANCH WOULD BE OK AS A WET VENT OR IF THE SYSTEM IS A |
| | CURCUIT VENT, A VERTICAL DRY VENT WOULD BE REQUIRED |
| | BETWEEN THE LAST TWO MOST UPSTREAM FIXTURE BRANCHES. |
| | 901.2.1 VENTING REQUIRED. |
| | EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN |
| | ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN |
| | THIS CHAPTER. |
| | 911.1 CIRCUIT VENT PERMITTED. |
| | 911.2 VENT CONNECTION. |
| | THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN |
| | THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL |
| | CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED |
| | IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE |
| | SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. |
| | |
| | 2. SHEETS P-1 & P-2: ALL HOSE BIBBS ARE REQUIRED TO |
| | HAVE SEPARATE SHUTOFF VALVES. |
| | 606.2 LOCATION OF SHUTOFF VALVES. |
| | (2) ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER |
| | THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| | |
| | 3. FLOOR DRAINS WILL BE REQUIRED TO HAVE TRAP PRIMERS. |
| | 1002.4 TRAP SEALS. |
| | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS |
| | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 |
| | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO |
| | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO |
| | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE |
| | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A |
| | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR |
| | ASSE 1044. |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |
| | FAX # 805-6676 |
| | |