| Plan Review Notes For Permit 13080851 |
| Permit Number |
13080851 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-04 11:14:17 | PLAN DENIED | | | 1) PROVIDE A DETAIL ON THE PLAN SHOWING CURB TO ROOF | | | TIEDOWN AND RTU TO CURB TIEDOWN. | | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | | 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLAN . | | | PER TABLE 403.3 FBC (M) 2010 | | | 3) ENERGY CALCULATIONS AND PLANS DO NOT MATCH. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|