| 2013-11-02 13:39:19 | 513 CLEMATIS STREET | | | PERMIT #13080797 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE UNIT DOORS (A,B, C), STORAGE ROOM DOOR, 1ST LEVEL | | | DOOR NEED TO HAVE A FIRE RESISTANCE RATING, LATCH, AND | | | AUTOMATIC CLOSER. WINDOWS TO BE FIRE RESISTANCE RATED | | | ALSO. SEE BELOW. | | | | | | NONE OF THE DOORS AND WINDOWS ADJACENT TO THE EXTERIOR | | | STAIRS ARE PROTECTED. PER NFPA 101 SECTION 7.2.2.6.3 | | | "SEPARATION AND PROTECTION OF OUTSIDE STAIRS: OUTSIDE | | | STAIRS SHALL BE SEPARATED FROM THE INTERIOR OF THE | | | BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE | | | RATING REQUIRED FOR ENCLOSED STAIRS WITH FIXED OR | | | SELF-CLOSING OPENING PROTECTIVES." WALL CONSTRUCTION | | | SHALL EXTEND AS FOLLOWS: (1) VERTICALLY FROM THE | | | FINISHED GROUND LEVEL TO A POINT 10 FEET ABOVE THE | | | TOPMOST LANDING OF THE STAIRS OR TO THE ROOFLINE, | | | WHICHEVER IS LOWER (2) HORIZONTALLY FOR NOT LESS THAN | | | 10 FEET. PER NFPA 101 SECTION 7.2.2.6.4 "PROTECTION OF | | | OPENINGS: ALL OPENINGS BELOW AN OUTSIDE STAIR SHALL BE | | | PROTECTED WITH AN ASSEMBLY HAVING A MINIMUM 45-MINUTE | | | FIRE PROTECTION RATING." | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|