| 2013-10-02 11:32:26 | BUILDING PLAN REVIEW |
| | PERMIT: 13080797 |
| | ADD: 513 CLEMATIS ST UNITS # 201, 203, & 205 |
| | CONT: LARRY B. ROWE |
| | TEL: (561)835-17999 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE:OCT 02/ 2013 |
| | ACTION: PROVISO |
| | |
| | 1) EGRESS COURT FOR THE REAR EXTERIOR STAIR IS TO |
| | COMPLY WITH: |
| | 2010 FBC-B 1027 EGRESS COURTS |
| | 1027.2 EXIT DISCHARGE CAPACITY. |
| | THE CAPACITY OF THE EXIT DISCHARGE SHALL BE NOT LESS |
| | THAN THE REQUIRED DISCHARGE CAPACITY OF THE EXITS BEING |
| | SERVED. |
| | |
| | 1027.3 EXIT DISCHARGE LOCATION. |
| | EXTERIOR BALCONIES, STAIRWAYS AND RAMPS SHALL BE |
| | LOCATED AT LEAST 10 FEET (3048 MM) FROM ADJACENT LOT |
| | LINES AND FROM OTHER BUILDINGS ON THE SAME LOT UNLESS |
| | THE ADJACENT BUILDING EXTERIOR WALLS AND OPENINGS ARE |
| | PROTECTED IN ACCORDANCE WITH SECTION 705 BASED ON FIRE |
| | SEPARATION DISTANCE. |
| | |
| | 1027.4 EXIT DISCHARGE COMPONENTS. |
| | EXIT DISCHARGE COMPONENTS SHALL BE SUFFICIENTLY OPEN TO |
| | THE EXTERIOR SO AS TO MINIMIZE THE ACCUMULATION OF |
| | SMOKE AND TOXIC GASES. |
| | |
| | 1027.5 EGRESS COURTS. |
| | EGRESS COURTS SERVING AS A PORTION OF THE EXIT |
| | DISCHARGE IN THE MEANS OF EGRESS SYSTEM SHALL COMPLY |
| | WITH THE REQUIREMENTS OF SECTION 1027. |
| | |
| | 1027.5.1 WIDTH. |
| | THE WIDTH OF EGRESS COURTS SHALL BE DETERMINED AS |
| | SPECIFIED IN SECTION 1005.1, BUT SUCH WIDTH SHALL NOT |
| | BE LESS THAN 44 INCHES (1118 MM), EXCEPT AS SPECIFIED |
| | HEREIN. EGRESS COURTS SERVING GROUP R-3 AND U |
| | OCCUPANCIES SHALL NOT BE LESS THAN 36 INCHES (914 MM) |
| | IN WIDTH. THE REQUIRED WIDTH OF EGRESS COURTS SHALL BE |
| | UNOBSTRUCTED TO A HEIGHT OF 7 FEET (2134 MM). |
| | |
| | WHERE AN EGRESS COURT EXCEEDS THE MINIMUM REQUIRED |
| | WIDTH AND THE WIDTH OF SUCH EGRESS COURT IS THEN |
| | REDUCED ALONG THE PATH OF EXIT TRAVEL, THE REDUCTION IN |
| | WIDTH SHALL BE GRADUAL. THE TRANSITION IN WIDTH SHALL |
| | BE AFFECTED BY A GUARD NOT LESS THAN 36 INCHES (914 MM) |
| | IN HEIGHT AND SHALL NOT CREATE AN ANGLE OF MORE THAN 30 |
| | DEGREES (0.52 RAD) WITH RESPECT TO THE AXIS OF THE |
| | EGRESS COURT ALONG THE PATH OF EGRESS TRAVEL. IN NO |
| | CASE SHALL THE WIDTH OF THE EGRESS COURT BE LESS THAN |
| | THE REQUIRED MINIMUM. |
| | |
| | 1027.5.2 CONSTRUCTION AND OPENINGS. |
| | WHERE AN EGRESS COURT SERVING A BUILDING OR PORTION |
| | THEREOF IS LESS THAN 10 FEET (3048 MM) IN WIDTH, THE |
| | EGRESS COURT WALLS SHALL HAVE NOT LESS THAN 1-HOUR |
| | FIRE-RESISTANCE-RATED CONSTRUCTION FOR A DISTANCE OF 10 |
| | FEET (3048 MM) ABOVE THE FLOOR OF THE COURT. OPENINGS |
| | WITHIN SUCH WALLS SHALL BE PROTECTED BY OPENING |
| | PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS |
| | THAN 3/4 HOUR. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |