| Notes |
| Date |
Text |
| 2013-10-02 10:39:20 | PLANS DENIED | | | 1) PROVIDE CALCULATION OF HEATING AND COOLING LOADS. | | | PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010 | | | 2) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS. | | | 2010 FLORIDA ENERGY CODE. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|