Plan Review Notes
Plan Review Notes For Permit 13080749
Permit Number 13080749
Review Stop M
Sequence Number 1
Notes
Date Text
2013-10-02 10:39:20PLANS DENIED
 1) PROVIDE CALCULATION OF HEATING AND COOLING LOADS.
 PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010
 2) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS.
 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  