Plan Review Notes
Plan Review Notes For Permit 13080749
Permit Number 13080749
Review Stop E
Sequence Number 1
Notes
Date Text
2013-09-25 15:48:019-25-13
 1. PROVIDE CONCRETE POLE DETAIL AND ENGINEERED WIND
 LOAD CALCS TO MEET SOUTH FLORIDA CODES
 2. TIME CLOCK FOR EXTERIOR LIGHTING CONTROLS REQUIRED 5
 TO HAVE 10 HOUR BACK-UP PER FLORIDA ENERGY CODE SECTION
 505.2.4
 3. PLEASE NOTE THAT ALL KITCHEN RECEPTS ARE TO BE GFCI
 PROTECTED PER NEC 210.8.B
 4. PLEASE NOTE THAT CONDUIT SEALING IS NEEDED FOR
 ENTERING OR LEAVING WALKIN COOLERS AND FREEZERS PER NEC
 300.7
 VB