| 2013-09-25 15:48:01 | 9-25-13 | | | 1. PROVIDE CONCRETE POLE DETAIL AND ENGINEERED WIND | | | LOAD CALCS TO MEET SOUTH FLORIDA CODES | | | 2. TIME CLOCK FOR EXTERIOR LIGHTING CONTROLS REQUIRED 5 | | | TO HAVE 10 HOUR BACK-UP PER FLORIDA ENERGY CODE SECTION | | | 505.2.4 | | | 3. PLEASE NOTE THAT ALL KITCHEN RECEPTS ARE TO BE GFCI | | | PROTECTED PER NEC 210.8.B | | | 4. PLEASE NOTE THAT CONDUIT SEALING IS NEEDED FOR | | | ENTERING OR LEAVING WALKIN COOLERS AND FREEZERS PER NEC | | | 300.7 | | | VB |
|