| 2013-10-17 13:31:26 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #2 | | | DENIED: | | | | | | COMMENTS FROM REVIEW #1 WERE NOT ADDESSED: | | | ONE RESTROOM WOULD BE OK FOR UP TO 25 PERSONS. FBC | | | PLUMBING 403.1 (1 PER 25 FOR THE FIRST 50 AND 1 PER 50 | | | FOR THE REMAINDER EXCEEDING 50). SHEET A2.01 LISTS | | | OCCUPANT LOAD AS 43. THE EXCEPTION SHOWN ON SHEET A0.01 | | | WOULD BE FOR AN OCCUPANT LOAD BASED ON SQUARE FEET (1 | | | PER 100 SQUARE FOOT). 43 OCCUPANTS WOULD REQUIRE 2 | | | FACILITIES PER TABLE 403.1 BUSINESS. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|