Plan Review Notes
Plan Review Notes For Permit 13080748
Permit Number 13080748
Review Stop P
Sequence Number 2
Notes
Date Text
2013-10-17 13:31:26FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #2
 DENIED:
  
 COMMENTS FROM REVIEW #1 WERE NOT ADDESSED:
 ONE RESTROOM WOULD BE OK FOR UP TO 25 PERSONS. FBC
 PLUMBING 403.1 (1 PER 25 FOR THE FIRST 50 AND 1 PER 50
 FOR THE REMAINDER EXCEEDING 50). SHEET A2.01 LISTS
 OCCUPANT LOAD AS 43. THE EXCEPTION SHOWN ON SHEET A0.01
 WOULD BE FOR AN OCCUPANT LOAD BASED ON SQUARE FEET (1
 PER 100 SQUARE FOOT). 43 OCCUPANTS WOULD REQUIRE 2
 FACILITIES PER TABLE 403.1 BUSINESS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  