Plan Review Notes
Plan Review Notes For Permit 13080748
Permit Number 13080748
Review Stop M
Sequence Number 1
Notes
Date Text
2013-09-19 17:09:33REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE CONDENSING UNIT ATTACHMENT DETAIL FOR WIND
 RESISTANCE PER FBC-M 301.12.
  
 2. PROVIDE CFMS FOR EACH GRILL/REGISTER ON PLANS PER
 FBC-M 603.1.
  
 3. PROVIDE SMOKE DETECTOR WITH FAN SHUT DOWN PER FBC-M
 606.2.1.
  
 4. AHU DETAIL SAYS TO "SEE PLUMBING FOR CONTINUATION"
 OF AUXILIARY DRAIN LINE. NO INFORMATION ON AUXILIARY
 DRAIN WAS FOUND ON PLUMBING DRAWINGS. PROVIDE AUXILIARY
 OR SECONDARY DRAIN PROTECTION PER FBC-M 307.2.3.
  