| 2013-09-19 17:09:33 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2010 | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PROVIDE CONDENSING UNIT ATTACHMENT DETAIL FOR WIND | | | RESISTANCE PER FBC-M 301.12. | | | | | | 2. PROVIDE CFMS FOR EACH GRILL/REGISTER ON PLANS PER | | | FBC-M 603.1. | | | | | | 3. PROVIDE SMOKE DETECTOR WITH FAN SHUT DOWN PER FBC-M | | | 606.2.1. | | | | | | 4. AHU DETAIL SAYS TO "SEE PLUMBING FOR CONTINUATION" | | | OF AUXILIARY DRAIN LINE. NO INFORMATION ON AUXILIARY | | | DRAIN WAS FOUND ON PLUMBING DRAWINGS. PROVIDE AUXILIARY | | | OR SECONDARY DRAIN PROTECTION PER FBC-M 307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|