2013-08-24 11:07:02PROVIDE MOTOR CALCULATION FOR INSTALLATION BASED ON NEC
 ARTICLE 430.
 CONDUCTORS DO NOT APPEAR TO BE SIZED FOR INRUSH AND/OR
 VOLTAGE DROP 430.250, 430 PART II, FLORIDA ENERGY CODE
 505.7.3 (NO DISTANCES SHOWN)
 PROVIDE DETAILS OF MOTOR CONTROL INCLUDING OVERLOAD
 PROTECTION 430.32
 PROVIDE DETAILS OF EQUIPMENT SHOWING SUITABILITY FOR
 THE INSTALLATION AND SUPPORTS 110.3, 110.8, 110.9,
 110.12, 110.13
 PLANS SHOW "FUTURE" BUILDING AND AS SUCH, DETAILS OF
 THE RACKING OR SUPPORT SYSTEM ARE NEEDED