Plan Review Notes
Plan Review Notes For Permit 13080721
Permit Number 13080721
Review Stop Z
Sequence Number 1
Notes
Date Text
2013-09-17 14:41:21FAILED
  
 1) THE PALM BEACH OUTLETS DESIGN GUIDELINES REQUIRE THE
 SCREENING OF THE ROOFTOP MECHANICAL EQUIPMENT.
  
 2) THE MECHANICAL PLANS SHOW THAT THE APPROVED ROOFTOP
 RTU IS BEING REPLACED BY 2 RTUS. PROVIDE INFORMATION ON
 THE HEIGHT OF THE RTUS, INCLUDING THE 14" CURB AND THE
 DISTANCE OF THE UNITS TO THE NORTHERN EDGE OF THE
 BUILDING.
  
 3) IF THE HEIGHT OF THE RTU PLUS THE CURB IS GREATER
 THAN 60 AND 7/8 INCHES OR CLOSER THAN 31 FEET TO THE
 NORTHERN EDGE OF THE BUILDING, THEN A REVISED SIGHT
 LINE STUDY FOR THE NEW RTU, WHICH DEMONSTRATES THAT THE
 RTU IS SCREENED, SHALL BE PROVIDED WITH THE PERMIT
 RESUBMITTAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.