2013-12-04 15:11:37PERMIT # 13080706
 PLAN REVIEW COMMENTS - FIRE DEPT
  
  
 1. A 1 HR SEPARATION WITH PROTECTED OPENINGS, DOORS,
 AND DUCT WORK IS REQUIRED FOR HAZARD SEPARATION WHERE
 STORAGE AREA AND SUPPLY STATION ARE LOCATED DUE TO
 INCREASED COMBUSTIBLES BEING LOCATED IN THIS AREA.
 2. CORRIDOR SHOWS TYPE X DRYWALL. IS THIS INTENDED TO
 BE A RATED COORIDOR? IF SO, PLEASE PROVIDE RATED
 WINDOWS AND DOORS AND PENETRATIONS. - SEE BUILDING
 COMMENTS
  
  