Plan Review Notes
Plan Review Notes For Permit 13080706
Permit Number 13080706
Review Stop M
Sequence Number 1
Notes
Date Text
2013-10-02 13:11:04PLANS DENIED
 1) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 (CAN'T HAVE WOOD DOORS) 2010 FBC (M)
 2) REFER TO SECTION 503.2.1 CALCULATION OF HEATING AND
 COOLING LOADS
 FLORIDA ENERGY CODE.
 3) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  