Plan Review Notes
Plan Review Notes For Permit 13080706
Permit Number 13080706
Review Stop E
Sequence Number 1
Notes
Date Text
2013-09-23 18:24:069-23-13
 1. ALL RECEPTACLES IN KITCHEN TO BE GFI PER NEC 210.8B.
 THERE ARE NO EXCEPTIONS LISTED
  
 2. FLUORESCENT FIXTURES REQUIRED INDIVIDUAL INTERNAL
 DISCONNECTS PER NEC 410.130G
  
 3. EXTERIOR LIGHTING MUST BE CONTROLLED PER FL ENERGY
 CODE SECTION 505.2.4
  