| Plan Review Notes For Permit 13080706 |
| Permit Number |
13080706 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-23 18:24:06 | 9-23-13 | | | 1. ALL RECEPTACLES IN KITCHEN TO BE GFI PER NEC 210.8B. | | | THERE ARE NO EXCEPTIONS LISTED | | | | | | 2. FLUORESCENT FIXTURES REQUIRED INDIVIDUAL INTERNAL | | | DISCONNECTS PER NEC 410.130G | | | | | | 3. EXTERIOR LIGHTING MUST BE CONTROLLED PER FL ENERGY | | | CODE SECTION 505.2.4 | | | | | | VB |
|