| 2013-09-16 16:00:46 | BUILDING PLAN REVIEW |
| | PERMIT: 13080706 |
| | ADD: 2107 N DIXIE HWY |
| | CONT: SERRAES CONSTRUCTION |
| | TEL: (561)848-6607 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SEPT 16/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET LS-1, UNDER THE HEADING NUMBER OF STORIES, THE |
| | PLAN INDICATES THIS BUILDING IS A ONE STORY BUILDING 20 |
| | FEET TALL? 107.2.1.3 WHAT IS ABOVE THIS SPACE, OR ARE |
| | THE WALLS RUNNING ALL THE WAY TO THE ROOF? 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 2) NEITHER LS-1 OR A-2 INDICATES THE USE OF FIRE RATED |
| | CORRIDORS, THE 2010 FBC TABLE 1018.1 REQUIRES A 1 HOUR |
| | FIRE RATED CORRIDOR IN A BUSINESS OCCUPANCY |
| | NON-SPRINKLERED BUILDING WITH A OCCUPANT LOAD OF |
| | GREATER THAN 30. BOTH THE 2007 FBC COMMENTARY AND BOAF |
| | INTERPRETATION 4849 AGREE. |
| | DATE: TUE JAN 9 2007 |
| | REPORT #: 4849 |
| | CODE: BUILDING |
| | SECTION: 1016 |
| | QUESTION: |
| | IS IT THE INTENT OF FBC SECTION 1016.1 TO REQUIRE |
| | 1?HOUR RATED EGRESS CORRIDORS IN A SINGLE TENANT |
| | NON?SPRINKLERED BUSINESS OCCUPANCY ALTHOUGH THE FLORIDA |
| | FIRE PREVENTION CODE 38.3.6 (2) PROVIDES AN |
| | EXCEPTION FOR CORRIDORS IN A SPACE OCCUPIED BY A SINGLE |
| | TENANT? |
| | ANSWER: |
| | YES, UNLESS THE EXCEPTION CAN BE MET TABLE 1016.1 |
| | REQUIRES A GROUP B OCCUPANCY TO HAVE 1 HOUR RATINGS |
| | FOR CORRIDORS SERVING OVER 30 IN AN UNSPRINKLED |
| | BUILDING. |
| | COMMENTARY: |
| | IF A CONFLICT WITH THE FFPC DOES EXIST, THE STRICTER |
| | REQUIREMENT GENERALLY PREVAILS. |
| | |
| | 3) NEITHER THE LS-1 OR A-2 SHOW FIRE RATED WALLS FOR |
| | THE LAUNDRY, PLEASE REVIEW 2010 FBC-B TABLE 508.2.5 |
| | LAUNDRIES 1 HOUR OR PROVIDE AN AUTOMATIC FIRE |
| | SUPRESSION SYSTEM. |
| | |
| | 4) PRODUCT APPROVAL FOR A SWING DOOR ARE ALSO INCLUDED |
| | IN THE PERMIT PACKAGE, SHEET A1 IS NOT CLEAR AS TO IF |
| | ONLY THE SWING DOOR AND FRAME ARE BEING REPLACED OR IF |
| | NEW OPENINGS ARE TO OCCUR. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |