2013-08-24 14:41:011. ELECTRICAL OUTLET SPACING DOES NOT APPEAR TO FULLY
 MEET 210.52. RECEPTACLE SPACING TO MEET THE
 REQUIREMENTS OF THE NEC AT THE TIME OF INSTALLATION.
 ALL UNITS, ALL DESIGNS
 2. SMOKE/CO ALARMS ARE TO BE LOCATED PER MANUFACTURERS
 INSTRUCTIONS FOR BEST AND MOST EFFICIENT OPERATION FOR
 EARLY WARNING, NOT AS SHOWN ON THE PLANS. ALL UNITS,
 ALL DESIGNS
 3. PLEASE INCLUDE PROVISO NOTE FOR EASEMENTS AND THE
 REQUIREMENT FOR RECORDING OF UTILITY EASEMENTS:
 A. THE LOCATION OF UNDERGROUND ELECTRICAL SERVICES,
 FEEDERS, CIRCUITS, ?HOUSE? CIRCUITS, ALL CONDUITS, AND
 OTHER APPURTENANCES, ASSOCIATED WITH THE PREMISE SYSTEM
 AND INSTALLED AT THE TIME OF THE FORMBOARD SURVEY,
 SHALL BE SHOWN ON THE FORMBOARD SURVEY.
 B. UTILITY AND PREMISE EASEMENTS, EASEMENT LOCATIONS,
 AND ASSOCIATED RESTRICTIVE PROPERTY COVENANTS ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL FOR REVIEW AND
 APPROVAL PRIOR TO RECORDING. SAID DOCUMENTS SHALL BE
 RECORDED AND PROOF OF RECORDING ON THE PLAT, AND
 ACCEPTANCE BY THE CITY SURVEYOR, SHALL BE PROVIDED
 PRIOR TO SCHEDULING OF ELECTRICAL ?ROUGH? INSPECTIONS.
 4. PROVIDE INTERSYSTEM BONDING POINT AT SERVICE PER
 250.94
 5. PLANS CALL FOR 2011 EDITION OF THE NEC. FLORIDA IS
 USING THE 2008 EDITION OF THE NEC AND ALL WORK IS TO
 COMPLY WITH THE ADOPTED STANDARDS AND REFERENCED
 DOCUMENTS IN ACCORDANCE WITH FLORIDA STATUTE 553.
 6. IDENTIFY UNITS AND SERVICES AT METERS AND
 DISCONNECTS. SERVICE MAINS DO NOT APPEAR TO AGREE WITH
 SERVICES AND CONDUCTOR SIZES.
 7. LOAD CALCULATION APPEARS TO BE MISSING. METER CENTER
 SHOWS A 200A AND ALL LOAD CALCULATIONS APPEAR TO BE FOR
 A 125 OR 150A SERVICE. PLEASE EXPLAIN, THIS DOES NOT
 APPEAR TO CORRESPOND WITH THE LOAD CALCULATION FOR THE
 BUILDING PROVIDED.
 8. ALL CONDUCTORS TO BE SIZED PER NEC 310.15. IF 90
 DEGREE C COLUMN IS TO BE USED, PROVIDE LISTING
 INFORMATION FOR ALL CONNECTIONS, CONDUIT AND OTHER
 PORTIONS OF THE ELECTRICAL SYSTEM TO ENSURE
 COMPATIBILITY. PLAN NOTES CALL FOR 75 DEGREE.
 9. DO SITE LIGHTING CONDUCTORS ACCOUNT FOR VOLTAGE
 DROP? FBC-EC 505.2
 10. NOTE 9 ON THE PLANS CALLS FOR TORQUEING OF ALUMINUM
 CONDUCTORS, NEC SECTION 110.13 CALLS FOR PROPER
 INSTALLATION OF ALL CONDUCTORS
 11. NOTE 10 CALLS FOR ANTI-OXIDANT AND WIRE BRUSHING OF
 AL CONDUCTORS. PLEASE PROVIDE MANUFACTURERS LISTING
 INFORMATION CALLING FOR THE PROPER APPLICATION AND
 MATERIALS. THIS MAY CONFLICT WITH NOTE 7.
  