| Plan Review Notes For Permit 13080645 |
| Permit Number |
13080645 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-09-03 10:21:42 | ***CORRECTIONS*** | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | | AT | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | 2ND REVIEW, SUBMITTED BUT NOT ALL COLUMNS WERE | | | COMPLETED. PLEASE COMPLETE THE FOLLOWING COLUMNS: WALL | | | PRESSURE, SHUTTER GLASS SEPARATION, SPAN (THIS IS BLADE | | | LENGTH OR ANCHOR TO ANCHOR, SHOULD BE ONE DIMENSION, | | | NOT TWO), AND EDGE DISTANCE. | | | | | | SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE WITH | | | ANCHOR CHART, SEE SHEET 7 (CONNECTION TYPES ARE NAMED 1 | | | THROUGH 8). | | | | | | 2. PROVIDE THE COVER SHEET FOR THE FLORIDA STATE | | | PRODUCT APPROVAL, FAC9N-3. THIS IS AVAILABLE AT | | | WWW.FLORIDABUILDING.ORG. THIS WILL INCLUDE THE APPROVAL | | | NUMBER AND THE STATUS, WHICH SHOULD BE "APPROVED." | | | | | | NOT ADDRESSED | | | | | | 3. TWO DIFFERENT EVALUATION REPORTS PROVIDED. THE | | | INSTALLATION SCHEDULE OR A REVISED FLOOR PLAN SHOULD | | | INDICATE WHICH OF THE PRODUCTS IS PROPOSED IN EACH | | | LOCATION. | | | | | | NOT ADDRESSED. |
|