| Notes |
| Date |
Text |
| 2013-10-03 16:24:22 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE EQUIPMENT SIZING CALCULATIONS RECOMMEND A 3 TON | | | SYSTEM (32,620 BTU) AND THE ENERGY CALCULATIONS SPECIFY | | | A 3.5 TON SYSTEM (42,000 BTU). THESE TWO DOCUMENTS | | | SHOULD MATCH. PLEASE CLARIFY. 2010 FBC ENERGY | | | CONSERVATION SECTION 101.4.7.1.2 NOTE: IT APPEARS THAT | | | THE ORIGINAL ENERGY CALCULATIONS WERE WORST CASE AND | | | THE NEW ONES ARE SITE SPECIFIC AS REQUIRED BY THE 2010 | | | ENERGY CODE. | | | | | | 2) SUBMIT TWO COPIES OF AN EQUIPMENT SCHEDULE | | | SPECIFYING THE MODEL NUMBERS AND OVERCURRENT PROTECTION | | | REQUIREMENTS. YOU CAN USE THE CITY OF WEST PALM BEACHES | | | A/C CHANGE OUT FORM FOR THIS. THE EQUIPMENT MUST MATCH | | | THE SIZING CALCULATIONS. 2010 FBC ENERGY CONSERVATION | | | SECTION 101.4.3 & TABLE 101.4.1 | | | | | | 3) BECAUSE THE DUCT WORK IS BEING REPLACED WITH NEW, | | | THE INSTALLATION SHALL COMPLY WITH FBCR M1602.4 FOR | | | BALANCED RETURN AIR. 2010 FBC ENERGY CONSERVATION | | | SECTION 101.4.3 & TABLE 101.4.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|