2013-09-16 16:09:59FIRST REVIEW - 9-16-13
  
 1. PROVIDE INTERSYSTEM BONDING BAR AT SERVICE PER NEC
 250.94
 2.PLEASE NOTE ALL NEW RECEPTS TO BE TAMPER RESISTANT
 TYPE PER NEC 406.11
 3. PLEASE NOTE THAT AFCI BREAKERS ARE REQUIRED TO
 PROTECT ALL NEW OUTLETS PER NEC 210.12B
 PLEASE SHOW CIRCUITS ON FLOOR PLAN FOR CLARITY
  
 VB