| Plan Review Notes For Permit 13080622 |
| Permit Number |
13080622 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-16 16:09:59 | FIRST REVIEW - 9-16-13 | | | | | | 1. PROVIDE INTERSYSTEM BONDING BAR AT SERVICE PER NEC | | | 250.94 | | | 2.PLEASE NOTE ALL NEW RECEPTS TO BE TAMPER RESISTANT | | | TYPE PER NEC 406.11 | | | 3. PLEASE NOTE THAT AFCI BREAKERS ARE REQUIRED TO | | | PROTECT ALL NEW OUTLETS PER NEC 210.12B | | | PLEASE SHOW CIRCUITS ON FLOOR PLAN FOR CLARITY | | | | | | VB |
|