2013-09-16 16:13:02PERMIT #13080598
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  