| 2013-09-18 14:29:52 | BUILDING PROVISO: | | | 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES. | | | EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH | | | THIS SECTION. | | | 4) EXCEPTION # 2 | | | 2.1 MEANS OF EGRESS ARE NOT PROHIBITED THROUGH | | | STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE | | | FOLLOWING ARE MET: | | | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS | | | THAT FOUND IN THE MAIN RETAIL AREA; | | | 2. .NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS | | | THROUGH THE STOCKROOM; | | | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE | | | EGRESS SIDE; AND | | | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 | | | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED | | | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE | | | REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA | | | TO THE EXIT WITHOUT OBSTRUCTIONS. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|