Plan Review Notes
Plan Review Notes For Permit 13080586
Permit Number 13080586
Review Stop B
Sequence Number 3
Notes
Date Text
2013-09-23 18:00:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 1. FBC 2010 RESIDENTIAL:
  
 SPANS NOT CORRECT, AND THEREFORE CANNOT DETERMINE
 WHETHER OR NOT ANCHOR SPACING OF 10" COMPLIES.
  
 FOR INSTANCE - OPENING 1, 47 X 86, SPAN IS SHOWN AS 4',
 VERTICAL INSTALLATION. 86" PLUS EDGE DISTANCE (1 1/2"
 TOP AND BOTTOM) SHOULD BE 89" SPAN. 8' SPAN, PANELMATE,
 60PSF (SEE PRODUCT APPROVAL) APPEARS TO REQUIRE 5"
 SPACING (PRODUCT APPROVAL SUBMITTED IS DIFFICULT TO
 READ).
  
 SPAN SHOULD BE THE DIMENSION OF ANCHOR TO ANCHOR.
  