| Plan Review Notes For Permit 13080586 |
| Permit Number |
13080586 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-09-11 19:09:25 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | | AT | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | COMPLIANCE CANNOT BE DETERMINED WITHOUT INFORMATION | | | SUCH AS SUBSTRATE. IT WOULD BE HELPFUL (BUT NOT | | | REQUIRED) IF THE SPECIFIC PROPOSED ANCHOR SPACING ON | | | THE CHART FROM THE PRODUCT APPROVAL IS CIRCLED AND | | | SUBMITTED. | | | | | | PLEASE NOTE THAT FOR HORIZONTAL INSTALLATION, SUBSTRATE | | | IS USUALLY FILLED CMU OR HOLLOW CMU, NOT CONCRETE. | | | | | | 2ND REVIEW - SAME PAPERWORK SUBMITTED. PLEASE SEE | | | SAMPLE FORM. THE CHART THAT WAS SUBMITTED LACKS | | | INFORMATION SUCH AS CONNECTION MOUNTING TYPE, EDGE | | | DISTANCE. PLEASE SEE THE FORM AT THE LINK PROVIDED | | | ABOVE OR IN THE LOBBY. | | | |
|