| 2013-08-21 18:44:17 | 901 NORTHPOINT PARKWAY - #400 |
| | PERMIT #13080577 |
| | MASTER #13060868 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | AN OPEN MASTER PERMIT (#13060868) ALREADY EXISTS FOR |
| | THIS LOCATION. IS THIS PERMIT TO BE VOIDED? |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE, NOT THE 2007 EDITION. |
| | |
| | PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE |
| | AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. |
| | |
| | PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED |
| | WALL ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM |
| | OR DEVICE. |
| | |
| | PROVIDE ADDITIONAL EMERGENCY LIGHTING; ONLY ONE FIXTURE |
| | IS CURRENTLY SHOWN. EMERGENCY ILLUMINATION SHALL BE |
| | PROVIDED FOR A MINIMUM OF 1.5 HOURS IN THE EVENT OF |
| | FAILURE OF NORMAL LIGHTING. EMERGENCY LIGHTING |
| | FACILITIES SHALL BE ARRANGED TO PROVIDE INITIAL |
| | ILLUMINATION THAT IS NOT LESS THAN AN AVERAGE OF 1 |
| | FT-CANDLE AND, AT ANY POINT, NOT LESS THAN 0.1 |
| | FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT FLOOR |
| | LEVEL. |
| | |
| | THE EXISTING FIRE BARRIER BETWEEN THE EDUCATIONAL |
| | OCCUPANCY AND THE BUSINESS OCCUPANCY (ADJACENT TENANT) |
| | NEEDS TO BE A 2-HOUR FIRE BARRIER. DURING A FIRE |
| | INSPECTION, MR. VINCE KENDRICK INDICATED THIS WAS A |
| | 2-HOUR FIRE BARRIER. THE PLAN INDICATES THIS WALL TO |
| | ONLY BE A 1-HOUR FIRE BARRIER. PLEASE VERIFY THE FIRE |
| | RATING OF THE EXISTING WALL. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |