2013-08-30 14:29:35FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
  
 1. SHEET 1 SHOWS THE RESTROOM AS 6'- 10" INSIDE. THE
 MINIMUM SIZE FOR THIS CONFIGURATION WOULD BE 7'- 1".
 FBC ACCESSIBILITY CODE 2010 604.3.1 SIZE. CLEARANCE
 AROUND A WATER CLOSET SHALL BE 60 INCHES (1525 MM)
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL
 NOT BE PERMITTED IN THE 60" SPACE.
 PLEASE ALSO SEE FIGURE 604.8.1.6.
  
 2. SHEET 1 THE SHOWER WILL BE REQUIRED TO BE
 ACCESSIBLE.
 FBC ACCESSIBILITY CODE 2010 608.1 - 608.8
  
 3. SHEET 1 THE SMALL SINK WILL BE REQUIRED TO HAVE THE
 COUNTER TOP NO HIGHER THAN 34" MAX.
 FBC ACCESSIBILITY CODE 2010 606.3
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  