| Plan Review Notes For Permit 13080516 |
| Permit Number |
13080516 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-09-28 08:56:11 | 721 VILLAGE BOULEVARD | | | PERMIT #13080516 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | REPEAT COMMENT: | | | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION | | | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES | | | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE | | | DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE | | | SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN ISSUED, | | | THE SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS | | | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) | | | FOR A SUB-PERMIT. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|