| Plan Review Notes For Permit 13080516 |
| Permit Number |
13080516 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-09-24 17:47:46 | BUILDING PROVISO: | | | SHEET A2.01 & A3.01 | | | DOOR # 4 | | | EXIT PASSAGEWAY | | | 2010 FBC-B 402.4.5.1. | | | 1 HOUR FIRE RATED DOOR ASSEMBLY | | | 402.4.5.1 EXIT PASSAGEWAYS. | | | WHERE EXIT PASSAGEWAYS PROVIDE A SECONDARY MEANS OF | | | EGRESS FROM A TENANT SPACE, | | | DOORWAYS TO THE EXIT PASSAGEWAY SHALL BE PROTECTED BY | | | 1-HOUR FIRE DOOR ASSEMBLIES THAT | | | ARE SELF- OR AUTOMATIC-CLOSING BY SMOKE DETECTION IN | | | ACCORDANCE WITH SECTION 715.4.8.3 | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|