Plan Review Notes
Plan Review Notes For Permit 13080516
Permit Number 13080516
Review Stop M
Sequence Number 1
Notes
Date Text
2013-09-09 11:45:07PLANS DENIED
 1) PROVIDE DUCT WORK ON 6.5 TON RTU ON PLANS.
 PER SECTION 107 FBC 2010.
 2) REFER TO SECTION 606.2.1 SUPPLY SYSTEMS
 ( DUCT DETECTOTS ) 606.3 INSTALLATION AND
 606.4.1 SUPERVISION. 2010 FBC (M)
 3) REFER TO SECTION 304.12 AREA SERVIED
 ( NUMBER RTU ) 2010 FBC (M)
 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS
 (FOR OUTSIDE AIR AND EXHAUST) 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER