| Plan Review Notes For Permit 13080516 |
| Permit Number |
13080516 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-09 11:45:07 | PLANS DENIED | | | 1) PROVIDE DUCT WORK ON 6.5 TON RTU ON PLANS. | | | PER SECTION 107 FBC 2010. | | | 2) REFER TO SECTION 606.2.1 SUPPLY SYSTEMS | | | ( DUCT DETECTOTS ) 606.3 INSTALLATION AND | | | 606.4.1 SUPERVISION. 2010 FBC (M) | | | 3) REFER TO SECTION 304.12 AREA SERVIED | | | ( NUMBER RTU ) 2010 FBC (M) | | | 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS | | | (FOR OUTSIDE AIR AND EXHAUST) 2010 FLORIDA ENERGY CODE. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|