| 2013-08-20 18:11:31 | 721 VILLAGE BOULEVARD |
| | PERMIT #13080516 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET A3.01: THE FOUR DOOR OPENINGS (DOOR TAG #4) INTO |
| | THE FIRE RATED EXIT CORRIDOR SHALL HAVE A FIRE |
| | RESISTANCE RATING OF AT LEAST 45 MINUTES. DOORS SHALL |
| | BE SELF-CLOSING AND POSITIVE LATCHING. |
| | |
| | SHEET M1: PROVIDE DUCT SMOKE DETECTION FOR NEW 6.5 TON |
| | AIR HANDLER. |
| | |
| | SHEET E1: INSUFFICIENT EMERGENCY LIGHTING PROVIDED IN |
| | EXIT CORRIDOR. |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES |
| | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE |
| | DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE |
| | SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN ISSUED, |
| | THE SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| | FOR A SUB-PERMIT. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |